🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 400 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.72%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.68V (5.66%)
Voltage at Load End11.8 VLoss: 0.2 V (8.2 W)
Power & Breaker (125%)0.48 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 400 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A100.35 V (836.25%)0.0 V165.53 V (1379.42%)4014.0 WDrop/Amp High
12 AWG3.31 mm²20 A63.06 V (525.5%)0.0 V104.02 V (866.82%)2522.4 WDrop/Amp High
10 AWG5.26 mm²30 A39.68 V (330.68%)0.0 V65.46 V (545.47%)1587.3 WDrop/Amp High
8 AWG8.37 mm²50 A24.94 V (207.81%)0.0 V41.14 V (342.79%)997.5 WDrop/Amp High
6 AWG13.3 mm²65 A15.69 V (130.78%)0.0 V25.89 V (215.73%)627.8 WDrop/Amp High
4 AWG21.15 mm²85 A9.87 V (82.24%)2.1 V16.28 V (135.66%)394.8 WDrop/Amp High
3 AWG26.67 mm²100 A7.83 V (65.22%)4.2 V12.91 V (107.58%)313.1 WDrop/Amp High
2 AWG33.62 mm²115 A6.21 V (51.74%)5.8 V10.24 V (85.34%)248.3 WDrop/Amp High
1 AWG42.41 mm²130 A4.92 V (41.01%)7.1 V8.12 V (67.65%)196.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.9 V (32.52%)8.1 V6.44 V (53.64%)156.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.1 V (25.8%)8.9 V5.11 V (42.55%)123.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.46 V (20.46%)9.5 V4.05 V (33.75%)98.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.95 V (16.23%)10.1 V3.21 V (26.76%)77.9 WDrop/Amp High
250 kcmil126.7 mm²255 A1.65 V (13.73%)10.4 V2.72 V (22.65%)65.9 WDrop/Amp High
300 kcmil152.0 mm²285 A1.37 V (11.44%)10.6 V2.27 V (18.88%)54.9 WDrop/Amp High
350 kcmil177.3 mm²310 A1.18 V (9.81%)10.8 V1.94 V (16.18%)47.1 WDrop/Amp High
400 kcmil202.7 mm²335 A1.03 V (8.58%)11.0 V1.7 V (14.15%)41.2 WDrop/Amp High
500 kcmil253.4 mm²380 A0.82 V (6.86%)11.2 V1.36 V (11.32%)32.9 WDrop/Amp High
600 kcmil304.0 mm²420 A0.69 V (5.72%)11.3 V1.13 V (9.44%)27.5 WDrop/Amp High
750 kcmil380.0 mm²475 A0.55 V (4.58%)11.5 V0.91 V (7.55%)22.0 W~ ≤5%
1000 kcmil506.7 mm²545 A0.41 V (3.43%)11.6 V0.68 V (5.66%)16.5 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 400 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 400 feet one-way at 12V (DC), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.2V (1.72%) and delivers 11.8V at the load.

What size aluminum wire is required for 40 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.68V (5.66%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.