⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

400 Amp Wire Size at 125 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 400 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 0.39%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.84V (0.38%)
Voltage at Load End478.1 VLoss: 1.86 V (1287.4 W)
Power & Breaker (125%)332.55 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 400 Amps at 125 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A271.58 V (56.58%)208.4 V447.98 V (93.33%)188155.4 WDrop/Amp High
12 AWG3.31 mm²20 A170.66 V (35.55%)309.3 V281.51 V (58.65%)118236.6 WDrop/Amp High
10 AWG5.26 mm²30 A107.39 V (22.37%)372.6 V177.15 V (36.91%)74403.7 WDrop/Amp High
8 AWG8.37 mm²50 A67.49 V (14.06%)412.5 V111.33 V (23.19%)46757.8 WDrop/Amp High
6 AWG13.3 mm²65 A42.47 V (8.85%)437.5 V70.06 V (14.6%)29425.8 WDrop/Amp High
4 AWG21.15 mm²85 A26.71 V (5.56%)453.3 V44.06 V (9.18%)18504.2 WDrop/Amp High
3 AWG26.67 mm²100 A21.18 V (4.41%)458.8 V34.94 V (7.28%)14674.3 WDrop/Amp High
2 AWG33.62 mm²115 A16.8 V (3.5%)463.2 V27.72 V (5.77%)11640.8 WDrop/Amp High
1 AWG42.41 mm²130 A13.32 V (2.77%)466.7 V21.97 V (4.58%)9228.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.56 V (2.2%)469.4 V17.42 V (3.63%)7316.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.38 V (1.75%)471.6 V13.82 V (2.88%)5804.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.64 V (1.38%)473.4 V10.96 V (2.28%)4603.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.27 V (1.1%)474.7 V8.69 V (1.81%)3650.8 WDrop/Amp High
250 kcmil126.7 mm²255 A4.46 V (0.93%)475.5 V7.35 V (1.53%)3088.9 WDrop/Amp High
300 kcmil152.0 mm²285 A3.72 V (0.77%)476.3 V6.13 V (1.28%)2574.8 WDrop/Amp High
350 kcmil177.3 mm²310 A3.19 V (0.66%)476.8 V5.26 V (1.09%)2207.4 WDrop/Amp High
400 kcmil202.7 mm²335 A2.79 V (0.58%)477.2 V4.6 V (0.96%)1930.8 WDrop/Amp High
500 kcmil253.4 mm²380 A2.23 V (0.46%)477.8 V3.68 V (0.77%)1544.4 WDrop/Amp High
600 kcmil304.0 mm²420 A1.86 V (0.39%)478.1 V3.07 V (0.64%)1287.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.49 V (0.31%)478.5 V2.45 V (0.51%)1029.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.11 V (0.23%)478.9 V1.84 V (0.38%)772.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 400 amps at 125 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 400A load over 125 feet one-way at 480V (3-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 1.86V (0.39%) and delivers 478.1V at the load.

What size aluminum wire is required for 400 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.84V (0.38%).

What breaker size is needed for a 400A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (400A × 1.25 = 500.0A), which corresponds to a standard 500A circuit breaker.