45 Amp Wire Size at 40 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.01%
Aluminum Wire (≤3% Drop)6 AWGDrop: 2.52V (1.05%)
Voltage at Load End237.6 VLoss: 2.43 V (189.4 W)
Power & Breaker (125%)18.71 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 40 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A9.78 V (4.07%)230.2 V16.13 V (6.72%)762.0 WDrop/Amp High
12 AWG3.31 mm²20 A6.14 V (2.56%)233.9 V10.13 V (4.22%)478.9 WDrop/Amp High
10 AWG5.26 mm²30 A3.87 V (1.61%)236.1 V6.38 V (2.66%)301.3 WDrop/Amp High
8 AWG8.37 mm²50 A2.43 V (1.01%)237.6 V4.01 V (1.67%)189.4 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.53 V (0.64%)238.5 V2.52 V (1.05%)119.2 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.96 V (0.4%)239.0 V1.59 V (0.66%)74.9 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.76 V (0.32%)239.2 V1.26 V (0.52%)59.4 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.6 V (0.25%)239.4 V1.0 V (0.42%)47.1 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.48 V (0.2%)239.5 V0.79 V (0.33%)37.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.38 V (0.16%)239.6 V0.63 V (0.26%)29.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.3 V (0.13%)239.7 V0.5 V (0.21%)23.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.24 V (0.1%)239.8 V0.39 V (0.16%)18.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.19 V (0.08%)239.8 V0.31 V (0.13%)14.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.16 V (0.07%)239.8 V0.26 V (0.11%)12.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.13 V (0.06%)239.9 V0.22 V (0.09%)10.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.11 V (0.05%)239.9 V0.19 V (0.08%)8.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.1 V (0.04%)239.9 V0.17 V (0.07%)7.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.08 V (0.03%)239.9 V0.13 V (0.06%)6.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.07 V (0.03%)239.9 V0.11 V (0.05%)5.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.05 V (0.02%)239.9 V0.09 V (0.04%)4.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.04 V (0.02%)240.0 V0.07 V (0.03%)3.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 40 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 40 feet one-way at 240V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 2.43V (1.01%) and delivers 237.6V at the load.

What size aluminum wire is required for 45 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 2.52V (1.05%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.