⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

450 Amp Wire Size at 1000 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 450 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.42%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 19.11V (7.96%)
Voltage at Load End234.2 VLoss: 5.79 V (2606.8 W)
Power & Breaker (125%)108.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 450 Amps at 1000 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2822.33 V (1175.97%)0.0 V4655.53 V (1939.8%)1270048.8 WDrop/Amp High
12 AWG3.31 mm²20 A1773.55 V (738.98%)0.0 V2925.53 V (1218.97%)798097.2 WDrop/Amp High
10 AWG5.26 mm²30 A1116.05 V (465.02%)0.0 V1840.97 V (767.07%)502224.6 WDrop/Amp High
8 AWG8.37 mm²50 A701.37 V (292.24%)0.0 V1156.93 V (482.05%)315615.5 WDrop/Amp High
6 AWG13.3 mm²65 A441.39 V (183.91%)0.0 V728.08 V (303.37%)198624.2 WDrop/Amp High
4 AWG21.15 mm²85 A277.56 V (115.65%)0.0 V457.85 V (190.77%)124903.1 WDrop/Amp High
3 AWG26.67 mm²100 A220.11 V (91.71%)19.9 V363.09 V (151.29%)99051.4 WDrop/Amp High
2 AWG33.62 mm²115 A174.61 V (72.75%)65.4 V288.03 V (120.01%)78575.3 WDrop/Amp High
1 AWG42.41 mm²130 A138.42 V (57.68%)101.6 V228.33 V (95.14%)62289.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A109.75 V (45.73%)130.3 V181.03 V (75.43%)49386.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A87.06 V (36.27%)152.9 V143.61 V (59.84%)39176.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A69.06 V (28.77%)170.9 V113.91 V (47.46%)31075.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A54.76 V (22.82%)185.2 V90.33 V (37.64%)24642.7 WDrop/Amp High
250 kcmil126.7 mm²255 A46.33 V (19.31%)193.7 V76.43 V (31.85%)20850.1 WDrop/Amp High
300 kcmil152.0 mm²285 A38.62 V (16.09%)201.4 V63.71 V (26.54%)17379.6 WDrop/Amp High
350 kcmil177.3 mm²310 A33.11 V (13.8%)206.9 V54.62 V (22.76%)14899.6 WDrop/Amp High
400 kcmil202.7 mm²335 A28.96 V (12.07%)211.0 V47.77 V (19.91%)13032.6 WDrop/Amp High
500 kcmil253.4 mm²380 A23.17 V (9.65%)216.8 V38.21 V (15.92%)10425.0 WDrop/Amp High
600 kcmil304.0 mm²420 A19.31 V (8.05%)220.7 V31.85 V (13.27%)8689.8 WDrop/Amp High
750 kcmil380.0 mm²475 A15.45 V (6.44%)224.6 V25.48 V (10.62%)6951.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A11.59 V (4.83%)228.4 V19.11 V (7.96%)5213.5 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 450 amps at 1000 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 450A load over 1000 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.79V (2.42%) and delivers 234.2V at the load.

What size aluminum wire is required for 450 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 19.11V (7.96%).

What breaker size is needed for a 450A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (450A × 1.25 = 562.5A), which corresponds to a standard 600A circuit breaker.