🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

100 Amp Wire Size at 1000 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 100 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 7.08V (2.95%)
Voltage at Load End233.6 VLoss: 6.44 V (643.6 W)
Power & Breaker (125%)24.0 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 100 Amps at 1000 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A627.18 V (261.33%)0.0 V1034.56 V (431.07%)62718.5 WDrop/Amp High
12 AWG3.31 mm²20 A394.12 V (164.22%)0.0 V650.12 V (270.88%)39412.2 WDrop/Amp High
10 AWG5.26 mm²30 A248.01 V (103.34%)0.0 V409.1 V (170.46%)24801.2 WDrop/Amp High
8 AWG8.37 mm²50 A155.86 V (64.94%)84.1 V257.1 V (107.12%)15585.9 WDrop/Amp High
6 AWG13.3 mm²65 A98.09 V (40.87%)141.9 V161.8 V (67.42%)9808.6 WDrop/Amp High
4 AWG21.15 mm²85 A61.68 V (25.7%)178.3 V101.74 V (42.39%)6168.1 WDrop/Amp High
3 AWG26.67 mm²100 A48.91 V (20.38%)191.1 V80.69 V (33.62%)4891.4 WDrop/Amp High
2 AWG33.62 mm²115 A38.8 V (16.17%)201.2 V64.01 V (26.67%)3880.3 WDrop/Amp High
1 AWG42.41 mm²130 A30.76 V (12.82%)209.2 V50.74 V (21.14%)3076.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A24.39 V (10.16%)215.6 V40.23 V (16.76%)2438.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A19.35 V (8.06%)220.7 V31.91 V (13.3%)1934.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A15.35 V (6.39%)224.7 V25.31 V (10.55%)1534.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.17 V (5.07%)227.8 V20.07 V (8.36%)1216.9 WDrop/Amp High
250 kcmil126.7 mm²255 A10.3 V (4.29%)229.7 V16.98 V (7.08%)1029.6 W~ ≤5%
300 kcmil152.0 mm²285 A8.58 V (3.58%)231.4 V14.16 V (5.9%)858.3 W~ ≤5%
350 kcmil177.3 mm²310 A7.36 V (3.07%)232.6 V12.14 V (5.06%)735.8 W~ ≤5%
400 kcmil202.7 mm²335 A6.44 V (2.68%)233.6 V10.62 V (4.42%)643.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A5.15 V (2.15%)234.9 V8.49 V (3.54%)514.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A4.29 V (1.79%)235.7 V7.08 V (2.95%)429.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.43 V (1.43%)236.6 V5.66 V (2.36%)343.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.57 V (1.07%)237.4 V4.25 V (1.77%)257.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 100 amps at 1000 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 100A load over 1000 feet one-way at 240V (1-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 6.44V (2.68%) and delivers 233.6V at the load.

What size aluminum wire is required for 100 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 7.08V (2.95%).

What breaker size is needed for a 100A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (100A × 1.25 = 125.0A), which corresponds to a standard 125A circuit breaker.