⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

450 Amp Wire Size at 175 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 450 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.98%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.9V (1.21%)
Voltage at Load End237.7 VLoss: 2.34 V (1824.9 W)
Power & Breaker (125%)187.06 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 450 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A427.74 V (178.22%)0.0 V705.57 V (293.99%)333387.8 WDrop/Amp High
12 AWG3.31 mm²20 A268.79 V (112.0%)0.0 V443.38 V (184.74%)209500.5 WDrop/Amp High
10 AWG5.26 mm²30 A169.14 V (70.48%)70.9 V279.01 V (116.25%)131834.0 WDrop/Amp High
8 AWG8.37 mm²50 A106.3 V (44.29%)133.7 V175.34 V (73.06%)82849.1 WDrop/Amp High
6 AWG13.3 mm²65 A66.89 V (27.87%)173.1 V110.34 V (45.98%)52138.8 WDrop/Amp High
4 AWG21.15 mm²85 A42.07 V (17.53%)197.9 V69.39 V (28.91%)32787.1 WDrop/Amp High
3 AWG26.67 mm²100 A33.36 V (13.9%)206.6 V55.03 V (22.93%)26001.0 WDrop/Amp High
2 AWG33.62 mm²115 A26.46 V (11.03%)213.5 V43.65 V (18.19%)20626.0 WDrop/Amp High
1 AWG42.41 mm²130 A20.98 V (8.74%)219.0 V34.6 V (14.42%)16351.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A16.63 V (6.93%)223.4 V27.44 V (11.43%)12964.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A13.19 V (5.5%)226.8 V21.76 V (9.07%)10283.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.47 V (4.36%)229.5 V17.26 V (7.19%)8157.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.3 V (3.46%)231.7 V13.69 V (5.7%)6468.7 WDrop/Amp High
250 kcmil126.7 mm²255 A7.02 V (2.93%)233.0 V11.58 V (4.83%)5473.1 WDrop/Amp High
300 kcmil152.0 mm²285 A5.85 V (2.44%)234.1 V9.66 V (4.02%)4562.1 WDrop/Amp High
350 kcmil177.3 mm²310 A5.02 V (2.09%)235.0 V8.28 V (3.45%)3911.1 WDrop/Amp High
400 kcmil202.7 mm²335 A4.39 V (1.83%)235.6 V7.24 V (3.02%)3421.0 WDrop/Amp High
500 kcmil253.4 mm²380 A3.51 V (1.46%)236.5 V5.79 V (2.41%)2736.6 WDrop/Amp High
600 kcmil304.0 mm²420 A2.93 V (1.22%)237.1 V4.83 V (2.01%)2281.1 WDrop/Amp High
750 kcmil380.0 mm²475 A2.34 V (0.98%)237.7 V3.86 V (1.61%)1824.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.76 V (0.73%)238.2 V2.9 V (1.21%)1368.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 450 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 450A load over 175 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 2.34V (0.98%) and delivers 237.7V at the load.

What size aluminum wire is required for 450 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.9V (1.21%).

What breaker size is needed for a 450A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (450A × 1.25 = 562.5A), which corresponds to a standard 600A circuit breaker.