⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

450 Amp Wire Size at 750 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 450 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.81%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 14.33V (5.97%)
Voltage at Load End235.7 VLoss: 4.34 V (1955.1 W)
Power & Breaker (125%)108.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 450 Amps at 750 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2116.75 V (881.98%)0.0 V3491.65 V (1454.85%)952536.6 WDrop/Amp High
12 AWG3.31 mm²20 A1330.16 V (554.23%)0.0 V2194.15 V (914.23%)598572.9 WDrop/Amp High
10 AWG5.26 mm²30 A837.04 V (348.77%)0.0 V1380.73 V (575.3%)376668.5 WDrop/Amp High
8 AWG8.37 mm²50 A526.03 V (219.18%)0.0 V867.7 V (361.54%)236711.6 WDrop/Amp High
6 AWG13.3 mm²65 A331.04 V (137.93%)0.0 V546.06 V (227.53%)148968.1 WDrop/Amp High
4 AWG21.15 mm²85 A208.17 V (86.74%)31.8 V343.39 V (143.08%)93677.4 WDrop/Amp High
3 AWG26.67 mm²100 A165.09 V (68.79%)74.9 V272.31 V (113.46%)74288.6 WDrop/Amp High
2 AWG33.62 mm²115 A130.96 V (54.57%)109.0 V216.02 V (90.01%)58931.5 WDrop/Amp High
1 AWG42.41 mm²130 A103.82 V (43.26%)136.2 V171.25 V (71.35%)46717.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A82.31 V (34.3%)157.7 V135.78 V (56.57%)37040.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A65.29 V (27.21%)174.7 V107.71 V (44.88%)29382.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A51.79 V (21.58%)188.2 V85.43 V (35.6%)23306.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A41.07 V (17.11%)198.9 V67.75 V (28.23%)18482.1 WDrop/Amp High
250 kcmil126.7 mm²255 A34.75 V (14.48%)205.2 V57.32 V (23.88%)15637.5 WDrop/Amp High
300 kcmil152.0 mm²285 A28.97 V (12.07%)211.0 V47.78 V (19.91%)13034.7 WDrop/Amp High
350 kcmil177.3 mm²310 A24.83 V (10.35%)215.2 V40.96 V (17.07%)11174.7 WDrop/Amp High
400 kcmil202.7 mm²335 A21.72 V (9.05%)218.3 V35.83 V (14.93%)9774.4 WDrop/Amp High
500 kcmil253.4 mm²380 A17.38 V (7.24%)222.6 V28.66 V (11.94%)7818.8 WDrop/Amp High
600 kcmil304.0 mm²420 A14.48 V (6.03%)225.5 V23.89 V (9.95%)6517.4 WDrop/Amp High
750 kcmil380.0 mm²475 A11.59 V (4.83%)228.4 V19.11 V (7.96%)5213.9 W~ ≤5%
1000 kcmil506.7 mm²545 A8.69 V (3.62%)231.3 V14.33 V (5.97%)3910.2 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 450 amps at 750 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 450A load over 750 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.34V (1.81%) and delivers 235.7V at the load.

What size aluminum wire is required for 450 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 14.33V (5.97%).

What breaker size is needed for a 450A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (450A × 1.25 = 562.5A), which corresponds to a standard 600A circuit breaker.