🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

5 Amp Wire Size at 150 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 5 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)14 AWG2.08 mm² · Drop: 1.7%
Aluminum Wire (≤3% Drop)14 AWGDrop: 6.72V (2.8%)
Voltage at Load End235.9 VLoss: 4.07 V (35.3 W)
Power & Breaker (125%)2.08 kW10A Breaker Recommended

All AWG & kcmil Wire Gauges for 5 Amps at 150 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A4.07 V (1.7%)235.9 V6.72 V (2.8%)35.3 W✓ PASS (≤3%)
12 AWG3.31 mm²20 A2.56 V (1.07%)237.4 V4.22 V (1.76%)22.2 W✓ PASS (≤3%)
10 AWG5.26 mm²30 A1.61 V (0.67%)238.4 V2.66 V (1.11%)14.0 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A1.01 V (0.42%)239.0 V1.67 V (0.7%)8.8 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A0.64 V (0.27%)239.4 V1.05 V (0.44%)5.5 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.4 V (0.17%)239.6 V0.66 V (0.28%)3.5 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.32 V (0.13%)239.7 V0.52 V (0.22%)2.8 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.25 V (0.11%)239.7 V0.42 V (0.17%)2.2 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.2 V (0.08%)239.8 V0.33 V (0.14%)1.7 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.16 V (0.07%)239.8 V0.26 V (0.11%)1.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.13 V (0.05%)239.9 V0.21 V (0.09%)1.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.1 V (0.04%)239.9 V0.16 V (0.07%)0.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.08 V (0.03%)239.9 V0.13 V (0.05%)0.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.07 V (0.03%)239.9 V0.11 V (0.05%)0.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.06 V (0.02%)239.9 V0.09 V (0.04%)0.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.05 V (0.02%)240.0 V0.08 V (0.03%)0.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.04 V (0.02%)240.0 V0.07 V (0.03%)0.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.03 V (0.01%)240.0 V0.06 V (0.02%)0.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.03 V (0.01%)240.0 V0.05 V (0.02%)0.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.02 V (0.01%)240.0 V0.04 V (0.02%)0.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.02 V (0.01%)240.0 V0.03 V (0.01%)0.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 5 amps at 150 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 5A load over 150 feet one-way at 240V (3-Phase), you need 14 AWG copper wire. This produces a voltage drop of 4.07V (1.7%) and delivers 235.9V at the load.

What size aluminum wire is required for 5 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 14 AWG to maintain voltage drop at 6.72V (2.8%).

What breaker size is needed for a 5A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (5A × 1.25 = 6.2A), which corresponds to a standard 10A circuit breaker.