🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

5 Amp Wire Size at 225 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 5 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)14 AWG2.08 mm² · Drop: 2.94%
Aluminum Wire (≤3% Drop)10 AWGDrop: 3.99V (1.92%)
Voltage at Load End201.9 VLoss: 6.11 V (52.9 W)
Power & Breaker (125%)1.8 kW10A Breaker Recommended

All AWG & kcmil Wire Gauges for 5 Amps at 225 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A6.11 V (2.94%)201.9 V10.08 V (4.85%)52.9 W✓ PASS (≤3%)
12 AWG3.31 mm²20 A3.84 V (1.85%)204.2 V6.33 V (3.05%)33.3 W✓ PASS (≤3%)
10 AWG5.26 mm²30 A2.42 V (1.16%)205.6 V3.99 V (1.92%)20.9 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A1.52 V (0.73%)206.5 V2.5 V (1.2%)13.2 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A0.96 V (0.46%)207.0 V1.58 V (0.76%)8.3 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.6 V (0.29%)207.4 V0.99 V (0.48%)5.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.48 V (0.23%)207.5 V0.79 V (0.38%)4.1 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.38 V (0.18%)207.6 V0.62 V (0.3%)3.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.3 V (0.14%)207.7 V0.49 V (0.24%)2.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.24 V (0.11%)207.8 V0.39 V (0.19%)2.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.19 V (0.09%)207.8 V0.31 V (0.15%)1.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.15 V (0.07%)207.9 V0.25 V (0.12%)1.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.12 V (0.06%)207.9 V0.2 V (0.09%)1.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.1 V (0.05%)207.9 V0.17 V (0.08%)0.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.08 V (0.04%)207.9 V0.14 V (0.07%)0.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.07 V (0.03%)207.9 V0.12 V (0.06%)0.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.06 V (0.03%)207.9 V0.1 V (0.05%)0.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.05 V (0.02%)207.9 V0.08 V (0.04%)0.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.04 V (0.02%)208.0 V0.07 V (0.03%)0.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.03 V (0.02%)208.0 V0.06 V (0.03%)0.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.03 V (0.01%)208.0 V0.04 V (0.02%)0.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 5 amps at 225 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 5A load over 225 feet one-way at 208V (3-Phase), you need 14 AWG copper wire. This produces a voltage drop of 6.11V (2.94%) and delivers 201.9V at the load.

What size aluminum wire is required for 5 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 10 AWG to maintain voltage drop at 3.99V (1.92%).

What breaker size is needed for a 5A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (5A × 1.25 = 6.2A), which corresponds to a standard 10A circuit breaker.