🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

5 Amp Wire Size at 250 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 5 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)10 AWG5.26 mm² · Drop: 2.58%
Aluminum Wire (≤3% Drop)8 AWGDrop: 3.21V (2.68%)
Voltage at Load End116.9 VLoss: 3.1 V (15.5 W)
Power & Breaker (125%)0.6 kW10A Breaker Recommended

All AWG & kcmil Wire Gauges for 5 Amps at 250 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A7.84 V (6.53%)112.2 V12.93 V (10.78%)39.2 WDrop/Amp High
12 AWG3.31 mm²20 A4.93 V (4.11%)115.1 V8.13 V (6.77%)24.6 W~ ≤5%
10 AWG5.26 mm²30 A3.1 V (2.58%)116.9 V5.11 V (4.26%)15.5 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A1.95 V (1.62%)118.1 V3.21 V (2.68%)9.7 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.23 V (1.02%)118.8 V2.02 V (1.69%)6.1 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.77 V (0.64%)119.2 V1.27 V (1.06%)3.9 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.61 V (0.51%)119.4 V1.01 V (0.84%)3.1 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.49 V (0.4%)119.5 V0.8 V (0.67%)2.4 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.38 V (0.32%)119.6 V0.63 V (0.53%)1.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.3 V (0.25%)119.7 V0.5 V (0.42%)1.5 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.24 V (0.2%)119.8 V0.4 V (0.33%)1.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.19 V (0.16%)119.8 V0.32 V (0.26%)1.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.15 V (0.13%)119.8 V0.25 V (0.21%)0.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.13 V (0.11%)119.9 V0.21 V (0.18%)0.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.11 V (0.09%)119.9 V0.18 V (0.15%)0.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.09 V (0.08%)119.9 V0.15 V (0.13%)0.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.08 V (0.07%)119.9 V0.13 V (0.11%)0.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.06 V (0.05%)119.9 V0.11 V (0.09%)0.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.05 V (0.04%)119.9 V0.09 V (0.07%)0.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.04 V (0.04%)120.0 V0.07 V (0.06%)0.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.03 V (0.03%)120.0 V0.05 V (0.04%)0.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 5 amps at 250 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 5A load over 250 feet one-way at 120V (1-Phase), you need 10 AWG copper wire. This produces a voltage drop of 3.1V (2.58%) and delivers 116.9V at the load.

What size aluminum wire is required for 5 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 3.21V (2.68%).

What breaker size is needed for a 5A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (5A × 1.25 = 6.2A), which corresponds to a standard 10A circuit breaker.