🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

15 Amp Wire Size at 250 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 15 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 1.93%
Aluminum Wire (≤3% Drop)3 AWGDrop: 3.03V (2.52%)
Voltage at Load End117.7 VLoss: 2.31 V (34.7 W)
Power & Breaker (125%)1.8 kW20A Breaker Recommended

All AWG & kcmil Wire Gauges for 15 Amps at 250 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A23.52 V (19.6%)96.5 V38.8 V (32.33%)352.8 WDrop/Amp High
12 AWG3.31 mm²20 A14.78 V (12.32%)105.2 V24.38 V (20.32%)221.7 WDrop/Amp High
10 AWG5.26 mm²30 A9.3 V (7.75%)110.7 V15.34 V (12.78%)139.5 WDrop/Amp High
8 AWG8.37 mm²50 A5.84 V (4.87%)114.2 V9.64 V (8.03%)87.7 W~ ≤5%
6 AWG13.3 mm²65 A3.68 V (3.07%)116.3 V6.07 V (5.06%)55.2 W~ ≤5%
4 AWG21.15 mm²85 A2.31 V (1.93%)117.7 V3.82 V (3.18%)34.7 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.83 V (1.53%)118.2 V3.03 V (2.52%)27.5 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.46 V (1.21%)118.5 V2.4 V (2.0%)21.8 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.15 V (0.96%)118.8 V1.9 V (1.59%)17.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.91 V (0.76%)119.1 V1.51 V (1.26%)13.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.73 V (0.6%)119.3 V1.2 V (1.0%)10.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.58 V (0.48%)119.4 V0.95 V (0.79%)8.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.46 V (0.38%)119.5 V0.75 V (0.63%)6.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.39 V (0.32%)119.6 V0.64 V (0.53%)5.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.32 V (0.27%)119.7 V0.53 V (0.44%)4.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.28 V (0.23%)119.7 V0.46 V (0.38%)4.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.24 V (0.2%)119.8 V0.4 V (0.33%)3.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.19 V (0.16%)119.8 V0.32 V (0.27%)2.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.16 V (0.13%)119.8 V0.27 V (0.22%)2.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.13 V (0.11%)119.9 V0.21 V (0.18%)1.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.1 V (0.08%)119.9 V0.16 V (0.13%)1.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 15 amps at 250 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 15A load over 250 feet one-way at 120V (1-Phase), you need 4 AWG copper wire. This produces a voltage drop of 2.31V (1.93%) and delivers 117.7V at the load.

What size aluminum wire is required for 15 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 3 AWG to maintain voltage drop at 3.03V (2.52%).

What breaker size is needed for a 15A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (15A × 1.25 = 18.8A), which corresponds to a standard 20A circuit breaker.