🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

5 Amp Wire Size at 275 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 5 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)10 AWG5.26 mm² · Drop: 2.84%
Aluminum Wire (≤3% Drop)8 AWGDrop: 3.54V (2.95%)
Voltage at Load End116.6 VLoss: 3.41 V (17.1 W)
Power & Breaker (125%)0.6 kW10A Breaker Recommended

All AWG & kcmil Wire Gauges for 5 Amps at 275 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A8.62 V (7.19%)111.4 V14.23 V (11.85%)43.1 WDrop/Amp High
12 AWG3.31 mm²20 A5.42 V (4.52%)114.6 V8.94 V (7.45%)27.1 W~ ≤5%
10 AWG5.26 mm²30 A3.41 V (2.84%)116.6 V5.63 V (4.69%)17.1 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A2.14 V (1.79%)117.9 V3.54 V (2.95%)10.7 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.35 V (1.12%)118.7 V2.22 V (1.85%)6.7 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.85 V (0.71%)119.2 V1.4 V (1.17%)4.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.67 V (0.56%)119.3 V1.11 V (0.92%)3.4 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.53 V (0.44%)119.5 V0.88 V (0.73%)2.7 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.42 V (0.35%)119.6 V0.7 V (0.58%)2.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.34 V (0.28%)119.7 V0.55 V (0.46%)1.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.27 V (0.22%)119.7 V0.44 V (0.37%)1.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.21 V (0.18%)119.8 V0.35 V (0.29%)1.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.17 V (0.14%)119.8 V0.28 V (0.23%)0.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.14 V (0.12%)119.9 V0.23 V (0.19%)0.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.12 V (0.1%)119.9 V0.19 V (0.16%)0.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.1 V (0.08%)119.9 V0.17 V (0.14%)0.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.09 V (0.07%)119.9 V0.15 V (0.12%)0.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.07 V (0.06%)119.9 V0.12 V (0.1%)0.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.06 V (0.05%)119.9 V0.1 V (0.08%)0.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.05 V (0.04%)120.0 V0.08 V (0.06%)0.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.04 V (0.03%)120.0 V0.06 V (0.05%)0.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 5 amps at 275 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 5A load over 275 feet one-way at 120V (1-Phase), you need 10 AWG copper wire. This produces a voltage drop of 3.41V (2.84%) and delivers 116.6V at the load.

What size aluminum wire is required for 5 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 3.54V (2.95%).

What breaker size is needed for a 5A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (5A × 1.25 = 6.2A), which corresponds to a standard 10A circuit breaker.