⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

5 Amp Wire Size at 300 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 5 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.95%
Aluminum Wire (≤3% Drop)6 AWGDrop: 2.43V (2.02%)
Voltage at Load End117.7 VLoss: 2.34 V (11.7 W)
Power & Breaker (125%)0.6 kW10A Breaker Recommended

All AWG & kcmil Wire Gauges for 5 Amps at 300 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A9.41 V (7.84%)110.6 V15.52 V (12.93%)47.0 WDrop/Amp High
12 AWG3.31 mm²20 A5.91 V (4.93%)114.1 V9.75 V (8.13%)29.6 W~ ≤5%
10 AWG5.26 mm²30 A3.72 V (3.1%)116.3 V6.14 V (5.11%)18.6 W~ ≤5%
8 AWG8.37 mm²50 A2.34 V (1.95%)117.7 V3.86 V (3.21%)11.7 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.47 V (1.23%)118.5 V2.43 V (2.02%)7.4 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.93 V (0.77%)119.1 V1.53 V (1.27%)4.6 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.73 V (0.61%)119.3 V1.21 V (1.01%)3.7 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.58 V (0.49%)119.4 V0.96 V (0.8%)2.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.46 V (0.38%)119.5 V0.76 V (0.63%)2.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.37 V (0.3%)119.6 V0.6 V (0.5%)1.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.29 V (0.24%)119.7 V0.48 V (0.4%)1.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.23 V (0.19%)119.8 V0.38 V (0.32%)1.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.18 V (0.15%)119.8 V0.3 V (0.25%)0.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.15 V (0.13%)119.8 V0.25 V (0.21%)0.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.13 V (0.11%)119.9 V0.21 V (0.18%)0.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.11 V (0.09%)119.9 V0.18 V (0.15%)0.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.1 V (0.08%)119.9 V0.16 V (0.13%)0.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.08 V (0.06%)119.9 V0.13 V (0.11%)0.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.06 V (0.05%)119.9 V0.11 V (0.09%)0.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.05 V (0.04%)119.9 V0.08 V (0.07%)0.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.04 V (0.03%)120.0 V0.06 V (0.05%)0.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 5 amps at 300 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 5A load over 300 feet one-way at 120V (1-Phase), you need 8 AWG copper wire. This produces a voltage drop of 2.34V (1.95%) and delivers 117.7V at the load.

What size aluminum wire is required for 5 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 2.43V (2.02%).

What breaker size is needed for a 5A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (5A × 1.25 = 6.2A), which corresponds to a standard 10A circuit breaker.