⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

50 Amp Wire Size at 75 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 50 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.11%
Aluminum Wire (≤3% Drop)6 AWGDrop: 5.25V (2.19%)
Voltage at Load End234.9 VLoss: 5.06 V (438.4 W)
Power & Breaker (125%)20.78 kW63A Breaker Recommended

All AWG & kcmil Wire Gauges for 50 Amps at 75 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A20.37 V (8.49%)219.6 V33.6 V (14.0%)1764.0 WDrop/Amp High
12 AWG3.31 mm²20 A12.8 V (5.33%)227.2 V21.11 V (8.8%)1108.5 WDrop/Amp High
10 AWG5.26 mm²30 A8.05 V (3.36%)231.9 V13.29 V (5.54%)697.5 WDrop/Amp High
8 AWG8.37 mm²50 A5.06 V (2.11%)234.9 V8.35 V (3.48%)438.4 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A3.19 V (1.33%)236.8 V5.25 V (2.19%)275.9 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.0 V (0.83%)238.0 V3.3 V (1.38%)173.5 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.59 V (0.66%)238.4 V2.62 V (1.09%)137.6 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.26 V (0.53%)238.7 V2.08 V (0.87%)109.1 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.0 V (0.42%)239.0 V1.65 V (0.69%)86.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.79 V (0.33%)239.2 V1.31 V (0.54%)68.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.63 V (0.26%)239.4 V1.04 V (0.43%)54.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.5 V (0.21%)239.5 V0.82 V (0.34%)43.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.4 V (0.16%)239.6 V0.65 V (0.27%)34.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.33 V (0.14%)239.7 V0.55 V (0.23%)29.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.28 V (0.12%)239.7 V0.46 V (0.19%)24.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.24 V (0.1%)239.8 V0.39 V (0.16%)20.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.21 V (0.09%)239.8 V0.34 V (0.14%)18.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.17 V (0.07%)239.8 V0.28 V (0.11%)14.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.14 V (0.06%)239.9 V0.23 V (0.1%)12.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.11 V (0.05%)239.9 V0.18 V (0.08%)9.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.08 V (0.03%)239.9 V0.14 V (0.06%)7.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 50 amps at 75 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 50A load over 75 feet one-way at 240V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 5.06V (2.11%) and delivers 234.9V at the load.

What size aluminum wire is required for 50 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 5.25V (2.19%).

What breaker size is needed for a 50A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (50A × 1.25 = 62.5A), which corresponds to a standard 63A circuit breaker.