🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

500 Amp Wire Size at 250 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 500 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 1.34%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.6V (2.21%)
Voltage at Load End205.2 VLoss: 2.79 V (2413.7 W)
Power & Breaker (125%)180.13 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 500 Amps at 250 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A678.95 V (326.42%)0.0 V1119.95 V (538.44%)587985.6 WDrop/Amp High
12 AWG3.31 mm²20 A426.65 V (205.12%)0.0 V703.77 V (338.35%)369489.4 WDrop/Amp High
10 AWG5.26 mm²30 A268.48 V (129.08%)0.0 V442.87 V (212.92%)232511.4 WDrop/Amp High
8 AWG8.37 mm²50 A168.72 V (81.12%)39.3 V278.31 V (133.8%)146118.3 WDrop/Amp High
6 AWG13.3 mm²65 A106.18 V (51.05%)101.8 V175.15 V (84.21%)91955.6 WDrop/Amp High
4 AWG21.15 mm²85 A66.77 V (32.1%)141.2 V110.14 V (52.95%)57825.5 WDrop/Amp High
3 AWG26.67 mm²100 A52.95 V (25.46%)155.0 V87.34 V (41.99%)45857.1 WDrop/Amp High
2 AWG33.62 mm²115 A42.01 V (20.19%)166.0 V69.29 V (33.31%)36377.5 WDrop/Amp High
1 AWG42.41 mm²130 A33.3 V (16.01%)174.7 V54.93 V (26.41%)28837.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A26.4 V (12.69%)181.6 V43.55 V (20.94%)22864.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A20.94 V (10.07%)187.1 V34.55 V (16.61%)18137.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A16.61 V (7.99%)191.4 V27.4 V (13.17%)14386.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A13.17 V (6.33%)194.8 V21.73 V (10.45%)11408.7 WDrop/Amp High
250 kcmil126.7 mm²255 A11.15 V (5.36%)196.9 V18.39 V (8.84%)9652.8 WDrop/Amp High
300 kcmil152.0 mm²285 A9.29 V (4.47%)198.7 V15.33 V (7.37%)8046.1 WDrop/Amp High
350 kcmil177.3 mm²310 A7.97 V (3.83%)200.0 V13.14 V (6.32%)6898.0 WDrop/Amp High
400 kcmil202.7 mm²335 A6.97 V (3.35%)201.0 V11.49 V (5.53%)6033.6 WDrop/Amp High
500 kcmil253.4 mm²380 A5.57 V (2.68%)202.4 V9.19 V (4.42%)4826.4 WDrop/Amp High
600 kcmil304.0 mm²420 A4.65 V (2.23%)203.4 V7.66 V (3.68%)4023.1 WDrop/Amp High
750 kcmil380.0 mm²475 A3.72 V (1.79%)204.3 V6.13 V (2.95%)3218.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.79 V (1.34%)205.2 V4.6 V (2.21%)2413.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 500 amps at 250 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 500A load over 250 feet one-way at 208V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 2.79V (1.34%) and delivers 205.2V at the load.

What size aluminum wire is required for 500 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.6V (2.21%).

What breaker size is needed for a 500A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (500A × 1.25 = 625.0A), which corresponds to a standard 700A circuit breaker.