⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

500 Amp Wire Size at 450 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 500 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.41%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 8.28V (3.98%)
Voltage at Load End203.0 VLoss: 5.02 V (4344.6 W)
Power & Breaker (125%)180.13 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 500 Amps at 450 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1222.11 V (587.55%)0.0 V2015.9 V (969.18%)1058374.0 WDrop/Amp High
12 AWG3.31 mm²20 A767.97 V (369.22%)0.0 V1266.79 V (609.03%)665081.0 WDrop/Amp High
10 AWG5.26 mm²30 A483.27 V (232.34%)0.0 V797.16 V (383.25%)418520.5 WDrop/Amp High
8 AWG8.37 mm²50 A303.7 V (146.01%)0.0 V500.96 V (240.85%)263012.9 WDrop/Amp High
6 AWG13.3 mm²65 A191.13 V (91.89%)16.9 V315.27 V (151.57%)165520.2 WDrop/Amp High
4 AWG21.15 mm²85 A120.19 V (57.78%)87.8 V198.25 V (95.31%)104086.0 WDrop/Amp High
3 AWG26.67 mm²100 A95.31 V (45.82%)112.7 V157.22 V (75.59%)82542.9 WDrop/Amp High
2 AWG33.62 mm²115 A75.61 V (36.35%)132.4 V124.72 V (59.96%)65479.4 WDrop/Amp High
1 AWG42.41 mm²130 A59.94 V (28.82%)148.1 V98.87 V (47.53%)51908.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A47.52 V (22.85%)160.5 V78.39 V (37.69%)41155.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A37.7 V (18.12%)170.3 V62.18 V (29.9%)32647.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A29.9 V (14.38%)178.1 V49.32 V (23.71%)25896.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A23.71 V (11.4%)184.3 V39.11 V (18.81%)20535.6 WDrop/Amp High
250 kcmil126.7 mm²255 A20.06 V (9.65%)187.9 V33.09 V (15.91%)17375.0 WDrop/Amp High
300 kcmil152.0 mm²285 A16.72 V (8.04%)191.3 V27.59 V (13.26%)14483.0 WDrop/Amp High
350 kcmil177.3 mm²310 A14.34 V (6.89%)193.7 V23.65 V (11.37%)12416.3 WDrop/Amp High
400 kcmil202.7 mm²335 A12.54 V (6.03%)195.5 V20.69 V (9.95%)10860.5 WDrop/Amp High
500 kcmil253.4 mm²380 A10.03 V (4.82%)198.0 V16.55 V (7.96%)8687.5 WDrop/Amp High
600 kcmil304.0 mm²420 A8.36 V (4.02%)199.6 V13.79 V (6.63%)7241.5 WDrop/Amp High
750 kcmil380.0 mm²475 A6.69 V (3.22%)201.3 V11.03 V (5.31%)5793.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.02 V (2.41%)203.0 V8.28 V (3.98%)4344.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 500 amps at 450 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 500A load over 450 feet one-way at 208V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 5.02V (2.41%) and delivers 203.0V at the load.

What size aluminum wire is required for 500 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 8.28V (3.98%).

What breaker size is needed for a 500A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (500A × 1.25 = 625.0A), which corresponds to a standard 700A circuit breaker.