🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 250 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)10× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.84V (48.66%)
Voltage at Load End11.7 VLoss: 0.35 V (194.7 W)
Power & Breaker (125%)6.6 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 250 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A862.38 V (7186.49%)0.0 V1422.52 V (11854.35%)474308.4 WDrop/Amp High
12 AWG3.31 mm²20 A541.92 V (4515.98%)0.0 V893.91 V (7449.26%)298054.8 WDrop/Amp High
10 AWG5.26 mm²30 A341.02 V (2841.81%)0.0 V562.52 V (4687.65%)187559.2 WDrop/Amp High
8 AWG8.37 mm²50 A214.31 V (1785.89%)0.0 V353.51 V (2945.88%)117868.7 WDrop/Amp High
6 AWG13.3 mm²65 A134.87 V (1123.9%)0.0 V222.47 V (1853.91%)74177.5 WDrop/Amp High
4 AWG21.15 mm²85 A84.81 V (706.76%)0.0 V139.9 V (1165.82%)46645.9 WDrop/Amp High
3 AWG26.67 mm²100 A67.26 V (560.48%)0.0 V110.94 V (924.52%)36991.4 WDrop/Amp High
2 AWG33.62 mm²115 A53.35 V (444.61%)0.0 V88.01 V (733.4%)29344.5 WDrop/Amp High
1 AWG42.41 mm²130 A42.3 V (352.46%)0.0 V69.77 V (581.4%)23262.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A33.53 V (279.45%)0.0 V55.32 V (460.97%)18443.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A26.6 V (221.68%)0.0 V43.88 V (365.67%)14630.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A21.1 V (175.84%)0.0 V34.81 V (290.05%)11605.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A16.73 V (139.44%)0.0 V27.6 V (230.01%)9203.0 WDrop/Amp High
250 kcmil126.7 mm²255 A14.16 V (117.98%)0.0 V23.35 V (194.61%)7786.6 WDrop/Amp High
300 kcmil152.0 mm²285 A11.8 V (98.34%)0.2 V19.47 V (162.22%)6490.5 WDrop/Amp High
350 kcmil177.3 mm²310 A10.12 V (84.31%)1.9 V16.69 V (139.07%)5564.4 WDrop/Amp High
400 kcmil202.7 mm²335 A8.85 V (73.74%)3.2 V14.6 V (121.64%)4867.1 WDrop/Amp High
500 kcmil253.4 mm²380 A7.08 V (58.99%)4.9 V11.68 V (97.3%)3893.3 WDrop/Amp High
600 kcmil304.0 mm²420 A5.9 V (49.17%)6.1 V9.73 V (81.11%)3245.3 WDrop/Amp High
750 kcmil380.0 mm²475 A4.72 V (39.34%)7.3 V7.79 V (64.89%)2596.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.54 V (29.5%)8.5 V5.84 V (48.66%)1947.0 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 250 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 250 feet one-way at 12V (DC), you need 10× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.95%) and delivers 11.7V at the load.

What size aluminum wire is required for 550 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.84V (48.66%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.