🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 80 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)4× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.36%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.87V (15.57%)
Voltage at Load End11.7 VLoss: 0.28 V (155.8 W)
Power & Breaker (125%)6.6 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 80 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A275.96 V (2299.68%)0.0 V455.21 V (3793.39%)151778.7 WDrop/Amp High
12 AWG3.31 mm²20 A173.41 V (1445.11%)0.0 V286.05 V (2383.76%)95377.5 WDrop/Amp High
10 AWG5.26 mm²30 A109.13 V (909.38%)0.0 V180.01 V (1500.05%)60018.9 WDrop/Amp High
8 AWG8.37 mm²50 A68.58 V (571.48%)0.0 V113.12 V (942.68%)37718.0 WDrop/Amp High
6 AWG13.3 mm²65 A43.16 V (359.65%)0.0 V71.19 V (593.25%)23736.8 WDrop/Amp High
4 AWG21.15 mm²85 A27.14 V (226.16%)0.0 V44.77 V (373.06%)14926.7 WDrop/Amp High
3 AWG26.67 mm²100 A21.52 V (179.35%)0.0 V35.5 V (295.85%)11837.3 WDrop/Amp High
2 AWG33.62 mm²115 A17.07 V (142.28%)0.0 V28.16 V (234.69%)9390.2 WDrop/Amp High
1 AWG42.41 mm²130 A13.53 V (112.79%)0.0 V22.33 V (186.05%)7444.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.73 V (89.42%)1.3 V17.7 V (147.51%)5902.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.51 V (70.94%)3.5 V14.04 V (117.01%)4681.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.75 V (56.27%)5.2 V11.14 V (92.82%)3713.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.35 V (44.62%)6.6 V8.83 V (73.6%)2945.0 WDrop/Amp High
250 kcmil126.7 mm²255 A4.53 V (37.75%)7.5 V7.47 V (62.28%)2491.7 WDrop/Amp High
300 kcmil152.0 mm²285 A3.78 V (31.47%)8.2 V6.23 V (51.91%)2077.0 WDrop/Amp High
350 kcmil177.3 mm²310 A3.24 V (26.98%)8.8 V5.34 V (44.5%)1780.6 WDrop/Amp High
400 kcmil202.7 mm²335 A2.83 V (23.6%)9.2 V4.67 V (38.93%)1557.5 WDrop/Amp High
500 kcmil253.4 mm²380 A2.27 V (18.88%)9.7 V3.74 V (31.14%)1245.9 WDrop/Amp High
600 kcmil304.0 mm²420 A1.89 V (15.73%)10.1 V3.11 V (25.95%)1038.5 WDrop/Amp High
750 kcmil380.0 mm²475 A1.51 V (12.59%)10.5 V2.49 V (20.76%)830.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.13 V (9.44%)10.9 V1.87 V (15.57%)623.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 80 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 80 feet one-way at 12V (DC), you need 4× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.28V (2.36%) and delivers 11.7V at the load.

What size aluminum wire is required for 550 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.87V (15.57%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.