🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 175 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)7× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.09V (34.06%)
Voltage at Load End11.7 VLoss: 0.35 V (194.7 W)
Power & Breaker (125%)6.6 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 175 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A603.67 V (5030.54%)0.0 V995.77 V (8298.05%)332015.9 WDrop/Amp High
12 AWG3.31 mm²20 A379.34 V (3161.19%)0.0 V625.74 V (5214.48%)208638.4 WDrop/Amp High
10 AWG5.26 mm²30 A238.71 V (1989.26%)0.0 V393.76 V (3281.36%)131291.4 WDrop/Amp High
8 AWG8.37 mm²50 A150.01 V (1250.12%)0.0 V247.45 V (2062.12%)82508.1 WDrop/Amp High
6 AWG13.3 mm²65 A94.41 V (786.73%)0.0 V155.73 V (1297.74%)51924.3 WDrop/Amp High
4 AWG21.15 mm²85 A59.37 V (494.73%)0.0 V97.93 V (816.07%)32652.2 WDrop/Amp High
3 AWG26.67 mm²100 A47.08 V (392.33%)0.0 V77.66 V (647.17%)25894.0 WDrop/Amp High
2 AWG33.62 mm²115 A37.35 V (311.23%)0.0 V61.61 V (513.38%)20541.1 WDrop/Amp High
1 AWG42.41 mm²130 A29.61 V (246.72%)0.0 V48.84 V (406.98%)16283.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A23.47 V (195.62%)0.0 V38.72 V (322.68%)12910.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A18.62 V (155.18%)0.0 V30.72 V (255.97%)10241.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A14.77 V (123.09%)0.0 V24.36 V (203.03%)8123.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A11.71 V (97.61%)0.3 V19.32 V (161.01%)6442.1 WDrop/Amp High
250 kcmil126.7 mm²255 A9.91 V (82.59%)2.1 V16.35 V (136.23%)5450.6 WDrop/Amp High
300 kcmil152.0 mm²285 A8.26 V (68.84%)3.7 V13.63 V (113.55%)4543.4 WDrop/Amp High
350 kcmil177.3 mm²310 A7.08 V (59.02%)4.9 V11.68 V (97.35%)3895.1 WDrop/Amp High
400 kcmil202.7 mm²335 A6.19 V (51.62%)5.8 V10.22 V (85.15%)3407.0 WDrop/Amp High
500 kcmil253.4 mm²380 A4.96 V (41.29%)7.0 V8.17 V (68.11%)2725.3 WDrop/Amp High
600 kcmil304.0 mm²420 A4.13 V (34.42%)7.9 V6.81 V (56.78%)2271.7 WDrop/Amp High
750 kcmil380.0 mm²475 A3.3 V (27.54%)8.7 V5.45 V (45.42%)1817.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.48 V (20.65%)9.5 V4.09 V (34.06%)1362.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 175 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 175 feet one-way at 12V (DC), you need 7× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.95%) and delivers 11.7V at the load.

What size aluminum wire is required for 550 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.09V (34.06%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.