⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

60 Amp Wire Size at 200 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 60 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 2.44%
Aluminum Wire (≤3% Drop)1 AWGDrop: 5.27V (2.54%)
Voltage at Load End202.9 VLoss: 5.08 V (528.3 W)
Power & Breaker (125%)21.62 kW80A Breaker Recommended

All AWG & kcmil Wire Gauges for 60 Amps at 200 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A65.18 V (31.34%)142.8 V107.51 V (51.69%)6773.6 WDrop/Amp High
12 AWG3.31 mm²20 A40.96 V (19.69%)167.0 V67.56 V (32.48%)4256.5 WDrop/Amp High
10 AWG5.26 mm²30 A25.77 V (12.39%)182.2 V42.52 V (20.44%)2678.5 WDrop/Amp High
8 AWG8.37 mm²50 A16.2 V (7.79%)191.8 V26.72 V (12.85%)1683.3 WDrop/Amp High
6 AWG13.3 mm²65 A10.19 V (4.9%)197.8 V16.81 V (8.08%)1059.3 W~ ≤5%
4 AWG21.15 mm²85 A6.41 V (3.08%)201.6 V10.57 V (5.08%)666.2 W~ ≤5%
3 AWG26.67 mm²100 A5.08 V (2.44%)202.9 V8.39 V (4.03%)528.3 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A4.03 V (1.94%)204.0 V6.65 V (3.2%)419.1 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A3.2 V (1.54%)204.8 V5.27 V (2.54%)332.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.53 V (1.22%)205.5 V4.18 V (2.01%)263.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.01 V (0.97%)206.0 V3.32 V (1.59%)208.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.59 V (0.77%)206.4 V2.63 V (1.26%)165.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.26 V (0.61%)206.7 V2.09 V (1.0%)131.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.07 V (0.51%)206.9 V1.77 V (0.85%)111.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.89 V (0.43%)207.1 V1.47 V (0.71%)92.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.76 V (0.37%)207.2 V1.26 V (0.61%)79.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.67 V (0.32%)207.3 V1.1 V (0.53%)69.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.54 V (0.26%)207.5 V0.88 V (0.42%)55.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.45 V (0.21%)207.6 V0.74 V (0.35%)46.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.36 V (0.17%)207.6 V0.59 V (0.28%)37.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.27 V (0.13%)207.7 V0.44 V (0.21%)27.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 60 amps at 200 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 60A load over 200 feet one-way at 208V (3-Phase), you need 3 AWG copper wire. This produces a voltage drop of 5.08V (2.44%) and delivers 202.9V at the load.

What size aluminum wire is required for 60 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 1 AWG to maintain voltage drop at 5.27V (2.54%).

What breaker size is needed for a 60A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (60A × 1.25 = 75.0A), which corresponds to a standard 80A circuit breaker.