🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

60 Amp Wire Size at 80 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 60 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 1.96%
Aluminum Wire (≤3% Drop)4 AWGDrop: 4.23V (2.03%)
Voltage at Load End203.9 VLoss: 4.08 V (423.7 W)
Power & Breaker (125%)21.62 kW80A Breaker Recommended

All AWG & kcmil Wire Gauges for 60 Amps at 80 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A26.07 V (12.53%)181.9 V43.01 V (20.68%)2709.4 WDrop/Amp High
12 AWG3.31 mm²20 A16.38 V (7.88%)191.6 V27.02 V (12.99%)1702.6 WDrop/Amp High
10 AWG5.26 mm²30 A10.31 V (4.96%)197.7 V17.01 V (8.18%)1071.4 WDrop/Amp High
8 AWG8.37 mm²50 A6.48 V (3.11%)201.5 V10.69 V (5.14%)673.3 WDrop/Amp High
6 AWG13.3 mm²65 A4.08 V (1.96%)203.9 V6.73 V (3.23%)423.7 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.56 V (1.23%)205.4 V4.23 V (2.03%)266.5 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.03 V (0.98%)206.0 V3.35 V (1.61%)211.3 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.61 V (0.78%)206.4 V2.66 V (1.28%)167.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.28 V (0.61%)206.7 V2.11 V (1.01%)132.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.01 V (0.49%)207.0 V1.67 V (0.8%)105.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.8 V (0.39%)207.2 V1.33 V (0.64%)83.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.64 V (0.31%)207.4 V1.05 V (0.51%)66.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.51 V (0.24%)207.5 V0.83 V (0.4%)52.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.43 V (0.21%)207.6 V0.71 V (0.34%)44.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.36 V (0.17%)207.6 V0.59 V (0.28%)37.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.31 V (0.15%)207.7 V0.5 V (0.24%)31.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.27 V (0.13%)207.7 V0.44 V (0.21%)27.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.21 V (0.1%)207.8 V0.35 V (0.17%)22.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.18 V (0.09%)207.8 V0.29 V (0.14%)18.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.14 V (0.07%)207.9 V0.24 V (0.11%)14.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.11 V (0.05%)207.9 V0.18 V (0.08%)11.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 60 amps at 80 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 60A load over 80 feet one-way at 208V (3-Phase), you need 6 AWG copper wire. This produces a voltage drop of 4.08V (1.96%) and delivers 203.9V at the load.

What size aluminum wire is required for 60 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 4.23V (2.03%).

What breaker size is needed for a 60A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (60A × 1.25 = 75.0A), which corresponds to a standard 80A circuit breaker.