🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 1000 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)5× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.57%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 25.48V (21.23%)
Voltage at Load End116.9 VLoss: 3.09 V (1853.7 W)
Power & Breaker (125%)72.0 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 1000 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3763.11 V (3135.92%)0.0 V6207.37 V (5172.81%)2257864.6 WDrop/Amp High
12 AWG3.31 mm²20 A2364.73 V (1970.61%)0.0 V3900.7 V (3250.59%)1418839.4 WDrop/Amp High
10 AWG5.26 mm²30 A1488.07 V (1240.06%)0.0 V2454.63 V (2045.52%)892843.8 WDrop/Amp High
8 AWG8.37 mm²50 A935.16 V (779.3%)0.0 V1542.57 V (1285.48%)561094.2 WDrop/Amp High
6 AWG13.3 mm²65 A588.52 V (490.43%)0.0 V970.78 V (808.98%)353109.7 WDrop/Amp High
4 AWG21.15 mm²85 A370.08 V (308.4%)0.0 V610.46 V (508.72%)222050.0 WDrop/Amp High
3 AWG26.67 mm²100 A293.49 V (244.57%)0.0 V484.11 V (403.43%)176091.4 WDrop/Amp High
2 AWG33.62 mm²115 A232.82 V (194.01%)0.0 V384.04 V (320.03%)139689.4 WDrop/Amp High
1 AWG42.41 mm²130 A184.56 V (153.8%)0.0 V304.44 V (253.7%)110737.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A146.33 V (121.94%)0.0 V241.38 V (201.15%)87798.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A116.08 V (96.73%)3.9 V191.48 V (159.56%)69647.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A92.07 V (76.73%)27.9 V151.88 V (126.57%)55244.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A73.02 V (60.85%)47.0 V120.44 V (100.37%)43809.3 WDrop/Amp High
250 kcmil126.7 mm²255 A61.78 V (51.48%)58.2 V101.9 V (84.92%)37066.8 WDrop/Amp High
300 kcmil152.0 mm²285 A51.5 V (42.91%)68.5 V84.94 V (70.79%)30897.1 WDrop/Amp High
350 kcmil177.3 mm²310 A44.15 V (36.79%)75.9 V72.82 V (60.68%)26488.2 WDrop/Amp High
400 kcmil202.7 mm²335 A38.62 V (32.18%)81.4 V63.7 V (53.08%)23169.0 WDrop/Amp High
500 kcmil253.4 mm²380 A30.89 V (25.74%)89.1 V50.95 V (42.46%)18533.4 WDrop/Amp High
600 kcmil304.0 mm²420 A25.75 V (21.46%)94.3 V42.47 V (35.39%)15448.5 WDrop/Amp High
750 kcmil380.0 mm²475 A20.6 V (17.17%)99.4 V33.98 V (28.31%)12358.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A15.45 V (12.87%)104.6 V25.48 V (21.23%)9268.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 1000 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 1000 feet one-way at 120V (1-Phase), you need 5× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.09V (2.57%) and delivers 116.9V at the load.

What size aluminum wire is required for 600 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 25.48V (21.23%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.