🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 60 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.39%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.53V (1.27%)
Voltage at Load End119.5 VLoss: 0.47 V (278.1 W)
Power & Breaker (125%)72.0 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 60 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A225.79 V (188.16%)0.0 V372.44 V (310.37%)135471.9 WDrop/Amp High
12 AWG3.31 mm²20 A141.88 V (118.24%)0.0 V234.04 V (195.04%)85130.4 WDrop/Amp High
10 AWG5.26 mm²30 A89.28 V (74.4%)30.7 V147.28 V (122.73%)53570.6 WDrop/Amp High
8 AWG8.37 mm²50 A56.11 V (46.76%)63.9 V92.55 V (77.13%)33665.7 WDrop/Amp High
6 AWG13.3 mm²65 A35.31 V (29.43%)84.7 V58.25 V (48.54%)21186.6 WDrop/Amp High
4 AWG21.15 mm²85 A22.21 V (18.5%)97.8 V36.63 V (30.52%)13323.0 WDrop/Amp High
3 AWG26.67 mm²100 A17.61 V (14.67%)102.4 V29.05 V (24.21%)10565.5 WDrop/Amp High
2 AWG33.62 mm²115 A13.97 V (11.64%)106.0 V23.04 V (19.2%)8381.4 WDrop/Amp High
1 AWG42.41 mm²130 A11.07 V (9.23%)108.9 V18.27 V (15.22%)6644.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.78 V (7.32%)111.2 V14.48 V (12.07%)5267.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.96 V (5.8%)113.0 V11.49 V (9.57%)4178.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.52 V (4.6%)114.5 V9.11 V (7.59%)3314.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.38 V (3.65%)115.6 V7.23 V (6.02%)2628.6 WDrop/Amp High
250 kcmil126.7 mm²255 A3.71 V (3.09%)116.3 V6.11 V (5.1%)2224.0 WDrop/Amp High
300 kcmil152.0 mm²285 A3.09 V (2.57%)116.9 V5.1 V (4.25%)1853.8 WDrop/Amp High
350 kcmil177.3 mm²310 A2.65 V (2.21%)117.4 V4.37 V (3.64%)1589.3 WDrop/Amp High
400 kcmil202.7 mm²335 A2.32 V (1.93%)117.7 V3.82 V (3.18%)1390.1 WDrop/Amp High
500 kcmil253.4 mm²380 A1.85 V (1.54%)118.1 V3.06 V (2.55%)1112.0 WDrop/Amp High
600 kcmil304.0 mm²420 A1.54 V (1.29%)118.5 V2.55 V (2.12%)926.9 WDrop/Amp High
750 kcmil380.0 mm²475 A1.24 V (1.03%)118.8 V2.04 V (1.7%)741.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.93 V (0.77%)119.1 V1.53 V (1.27%)556.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 60 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 60 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.47V (0.39%) and delivers 119.5V at the load.

What size aluminum wire is required for 600 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.53V (1.27%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.