🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 300 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)13× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.97%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.64V (63.7%)
Voltage at Load End11.6 VLoss: 0.36 V (213.9 W)
Power & Breaker (125%)7.2 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 300 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1128.93 V (9407.77%)0.0 V1862.21 V (15518.42%)677359.4 WDrop/Amp High
12 AWG3.31 mm²20 A709.42 V (5911.83%)0.0 V1170.21 V (9751.76%)425651.8 WDrop/Amp High
10 AWG5.26 mm²30 A446.42 V (3720.18%)0.0 V736.39 V (6136.56%)267853.1 WDrop/Amp High
8 AWG8.37 mm²50 A280.55 V (2337.89%)0.0 V462.77 V (3856.43%)168328.3 WDrop/Amp High
6 AWG13.3 mm²65 A176.55 V (1471.29%)0.0 V291.23 V (2426.94%)105932.9 WDrop/Amp High
4 AWG21.15 mm²85 A111.03 V (925.21%)0.0 V183.14 V (1526.16%)66615.0 WDrop/Amp High
3 AWG26.67 mm²100 A88.05 V (733.71%)0.0 V145.23 V (1210.29%)52827.4 WDrop/Amp High
2 AWG33.62 mm²115 A69.84 V (582.04%)0.0 V115.21 V (960.09%)41906.8 WDrop/Amp High
1 AWG42.41 mm²130 A55.37 V (461.4%)0.0 V91.33 V (761.1%)33221.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A43.9 V (365.83%)0.0 V72.41 V (603.45%)26339.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A34.82 V (290.2%)0.0 V57.44 V (478.69%)20894.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A27.62 V (230.19%)0.0 V45.56 V (379.7%)16573.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A21.9 V (182.54%)0.0 V36.13 V (301.1%)13142.8 WDrop/Amp High
250 kcmil126.7 mm²255 A18.53 V (154.44%)0.0 V30.57 V (254.76%)11120.0 WDrop/Amp High
300 kcmil152.0 mm²285 A15.45 V (128.74%)0.0 V25.48 V (212.36%)9269.1 WDrop/Amp High
350 kcmil177.3 mm²310 A13.24 V (110.37%)0.0 V21.85 V (182.05%)7946.5 WDrop/Amp High
400 kcmil202.7 mm²335 A11.58 V (96.54%)0.4 V19.11 V (159.24%)6950.7 WDrop/Amp High
500 kcmil253.4 mm²380 A9.27 V (77.22%)2.7 V15.29 V (127.38%)5560.0 WDrop/Amp High
600 kcmil304.0 mm²420 A7.72 V (64.37%)4.3 V12.74 V (106.18%)4634.6 WDrop/Amp High
750 kcmil380.0 mm²475 A6.18 V (51.5%)5.8 V10.19 V (84.94%)3707.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A4.63 V (38.62%)7.4 V7.64 V (63.7%)2780.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 300 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 300 feet one-way at 12V (DC), you need 13× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.36V (2.97%) and delivers 11.6V at the load.

What size aluminum wire is required for 600 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.64V (63.7%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.