⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 150 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)7× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.76%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.82V (31.85%)
Voltage at Load End11.7 VLoss: 0.33 V (198.6 W)
Power & Breaker (125%)7.2 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 150 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A564.47 V (4703.88%)0.0 V931.11 V (7759.21%)338679.7 WDrop/Amp High
12 AWG3.31 mm²20 A354.71 V (2955.92%)0.0 V585.11 V (4875.88%)212825.9 WDrop/Amp High
10 AWG5.26 mm²30 A223.21 V (1860.09%)0.0 V368.19 V (3068.28%)133926.6 WDrop/Amp High
8 AWG8.37 mm²50 A140.27 V (1168.95%)0.0 V231.39 V (1928.22%)84164.1 WDrop/Amp High
6 AWG13.3 mm²65 A88.28 V (735.65%)0.0 V145.62 V (1213.47%)52966.4 WDrop/Amp High
4 AWG21.15 mm²85 A55.51 V (462.6%)0.0 V91.57 V (763.08%)33307.5 WDrop/Amp High
3 AWG26.67 mm²100 A44.02 V (366.86%)0.0 V72.62 V (605.14%)26413.7 WDrop/Amp High
2 AWG33.62 mm²115 A34.92 V (291.02%)0.0 V57.61 V (480.05%)20953.4 WDrop/Amp High
1 AWG42.41 mm²130 A27.68 V (230.7%)0.0 V45.67 V (380.55%)16610.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A21.95 V (182.91%)0.0 V36.21 V (301.72%)13169.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A17.41 V (145.1%)0.0 V28.72 V (239.35%)10447.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A13.81 V (115.09%)0.0 V22.78 V (189.85%)8286.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.95 V (91.27%)1.0 V18.07 V (150.55%)6571.4 WDrop/Amp High
250 kcmil126.7 mm²255 A9.27 V (77.22%)2.7 V15.29 V (127.38%)5560.0 WDrop/Amp High
300 kcmil152.0 mm²285 A7.72 V (64.37%)4.3 V12.74 V (106.18%)4634.6 WDrop/Amp High
350 kcmil177.3 mm²310 A6.62 V (55.18%)5.4 V10.92 V (91.03%)3973.2 WDrop/Amp High
400 kcmil202.7 mm²335 A5.79 V (48.27%)6.2 V9.55 V (79.62%)3475.4 WDrop/Amp High
500 kcmil253.4 mm²380 A4.63 V (38.61%)7.4 V7.64 V (63.69%)2780.0 WDrop/Amp High
600 kcmil304.0 mm²420 A3.86 V (32.18%)8.1 V6.37 V (53.09%)2317.3 WDrop/Amp High
750 kcmil380.0 mm²475 A3.09 V (25.75%)8.9 V5.1 V (42.47%)1853.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.32 V (19.31%)9.7 V3.82 V (31.85%)1390.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 150 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 150 feet one-way at 12V (DC), you need 7× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.33V (2.76%) and delivers 11.7V at the load.

What size aluminum wire is required for 600 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.82V (31.85%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.