🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 450 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.62%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.93V (2.07%)
Voltage at Load End477.0 VLoss: 3.01 V (3128.2 W)
Power & Breaker (125%)498.83 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 450 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1466.53 V (305.53%)0.0 V2419.08 V (503.98%)1524058.6 WDrop/Amp High
12 AWG3.31 mm²20 A921.56 V (191.99%)0.0 V1520.15 V (316.7%)957716.6 WDrop/Amp High
10 AWG5.26 mm²30 A579.92 V (120.82%)0.0 V956.6 V (199.29%)602669.6 WDrop/Amp High
8 AWG8.37 mm²50 A364.44 V (75.93%)115.6 V601.16 V (125.24%)378738.6 WDrop/Amp High
6 AWG13.3 mm²65 A229.35 V (47.78%)250.6 V378.32 V (78.82%)238349.0 WDrop/Amp High
4 AWG21.15 mm²85 A144.23 V (30.05%)335.8 V237.91 V (49.56%)149883.8 WDrop/Amp High
3 AWG26.67 mm²100 A114.37 V (23.83%)365.6 V188.66 V (39.31%)118861.7 WDrop/Amp High
2 AWG33.62 mm²115 A90.73 V (18.9%)389.3 V149.66 V (31.18%)94290.4 WDrop/Amp High
1 AWG42.41 mm²130 A71.93 V (14.98%)408.1 V118.64 V (24.72%)74747.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A57.03 V (11.88%)423.0 V94.07 V (19.6%)59264.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A45.24 V (9.42%)434.8 V74.62 V (15.55%)47012.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A35.88 V (7.48%)444.1 V59.19 V (12.33%)37290.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A28.45 V (5.93%)451.5 V46.94 V (9.78%)29571.3 WDrop/Amp High
250 kcmil126.7 mm²255 A24.08 V (5.02%)455.9 V39.71 V (8.27%)25020.1 WDrop/Amp High
300 kcmil152.0 mm²285 A20.07 V (4.18%)459.9 V33.1 V (6.9%)20855.5 WDrop/Amp High
350 kcmil177.3 mm²310 A17.2 V (3.58%)462.8 V28.38 V (5.91%)17879.5 WDrop/Amp High
400 kcmil202.7 mm²335 A15.05 V (3.14%)465.0 V24.82 V (5.17%)15639.1 WDrop/Amp High
500 kcmil253.4 mm²380 A12.04 V (2.51%)468.0 V19.86 V (4.14%)12510.0 WDrop/Amp High
600 kcmil304.0 mm²420 A10.03 V (2.09%)470.0 V16.55 V (3.45%)10427.8 WDrop/Amp High
750 kcmil380.0 mm²475 A8.03 V (1.67%)472.0 V13.24 V (2.76%)8342.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A6.02 V (1.25%)474.0 V9.93 V (2.07%)6256.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 450 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 450 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.01V (0.62%) and delivers 477.0V at the load.

What size aluminum wire is required for 600 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.93V (2.07%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.