⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 450 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)1/0 AWG53.49 mm² · Drop: 2.48%
Aluminum Wire (≤3% Drop)3/0 AWGDrop: 12.33V (2.57%)
Voltage at Load End468.1 VLoss: 11.88 V (2572.2 W)
Power & Breaker (125%)103.92 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 450 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A305.53 V (63.65%)174.5 V503.98 V (104.99%)66148.4 WDrop/Amp High
12 AWG3.31 mm²20 A191.99 V (40.0%)288.0 V316.7 V (65.98%)41567.6 WDrop/Amp High
10 AWG5.26 mm²30 A120.82 V (25.17%)359.2 V199.29 V (41.52%)26157.5 WDrop/Amp High
8 AWG8.37 mm²50 A75.93 V (15.82%)404.1 V125.24 V (26.09%)16438.3 WDrop/Amp High
6 AWG13.3 mm²65 A47.78 V (9.95%)432.2 V78.82 V (16.42%)10345.0 WDrop/Amp High
4 AWG21.15 mm²85 A30.05 V (6.26%)450.0 V49.56 V (10.33%)6505.4 WDrop/Amp High
3 AWG26.67 mm²100 A23.83 V (4.96%)456.2 V39.31 V (8.19%)5158.9 WDrop/Amp High
2 AWG33.62 mm²115 A18.9 V (3.94%)461.1 V31.18 V (6.5%)4092.5 WDrop/Amp High
1 AWG42.41 mm²130 A14.98 V (3.12%)465.0 V24.72 V (5.15%)3244.2 W~ ≤5%
1/0 AWG53.49 mm²150 A11.88 V (2.48%)468.1 V19.6 V (4.08%)2572.2 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A9.42 V (1.96%)470.6 V15.55 V (3.24%)2040.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A7.48 V (1.56%)472.5 V12.33 V (2.57%)1618.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A5.93 V (1.24%)474.1 V9.78 V (2.04%)1283.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A5.02 V (1.04%)475.0 V8.27 V (1.72%)1085.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A4.18 V (0.87%)475.8 V6.9 V (1.44%)905.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.58 V (0.75%)476.4 V5.91 V (1.23%)776.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.14 V (0.65%)476.9 V5.17 V (1.08%)678.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.51 V (0.52%)477.5 V4.14 V (0.86%)543.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.09 V (0.44%)477.9 V3.45 V (0.72%)452.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.67 V (0.35%)478.3 V2.76 V (0.57%)362.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.25 V (0.26%)478.7 V2.07 V (0.43%)271.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 450 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 450 feet one-way at 480V (3-Phase), you need 1/0 AWG copper wire. This produces a voltage drop of 11.88V (2.48%) and delivers 468.1V at the load.

What size aluminum wire is required for 125 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 3/0 AWG to maintain voltage drop at 12.33V (2.57%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.