🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

50 Amp Wire Size at 450 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 50 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.5%
Aluminum Wire (≤3% Drop)2 AWGDrop: 12.47V (2.6%)
Voltage at Load End468.0 VLoss: 12.02 V (1040.9 W)
Power & Breaker (125%)41.57 kW63A Breaker Recommended

All AWG & kcmil Wire Gauges for 50 Amps at 450 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A122.21 V (25.46%)357.8 V201.59 V (42.0%)10583.7 WDrop/Amp High
12 AWG3.31 mm²20 A76.8 V (16.0%)403.2 V126.68 V (26.39%)6650.8 WDrop/Amp High
10 AWG5.26 mm²30 A48.33 V (10.07%)431.7 V79.72 V (16.61%)4185.2 WDrop/Amp High
8 AWG8.37 mm²50 A30.37 V (6.33%)449.6 V50.1 V (10.44%)2630.1 WDrop/Amp High
6 AWG13.3 mm²65 A19.11 V (3.98%)460.9 V31.53 V (6.57%)1655.2 W~ ≤5%
4 AWG21.15 mm²85 A12.02 V (2.5%)468.0 V19.83 V (4.13%)1040.9 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A9.53 V (1.99%)470.5 V15.72 V (3.28%)825.4 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A7.56 V (1.58%)472.4 V12.47 V (2.6%)654.8 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A5.99 V (1.25%)474.0 V9.89 V (2.06%)519.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A4.75 V (0.99%)475.2 V7.84 V (1.63%)411.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A3.77 V (0.79%)476.2 V6.22 V (1.3%)326.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.99 V (0.62%)477.0 V4.93 V (1.03%)259.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.37 V (0.49%)477.6 V3.91 V (0.81%)205.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.01 V (0.42%)478.0 V3.31 V (0.69%)173.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.67 V (0.35%)478.3 V2.76 V (0.57%)144.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.43 V (0.3%)478.6 V2.36 V (0.49%)124.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.25 V (0.26%)478.7 V2.07 V (0.43%)108.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.0 V (0.21%)479.0 V1.65 V (0.34%)86.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.84 V (0.17%)479.2 V1.38 V (0.29%)72.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.67 V (0.14%)479.3 V1.1 V (0.23%)57.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.5 V (0.1%)479.5 V0.83 V (0.17%)43.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 50 amps at 450 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 50A load over 450 feet one-way at 480V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 12.02V (2.5%) and delivers 468.0V at the load.

What size aluminum wire is required for 50 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 12.47V (2.6%).

What breaker size is needed for a 50A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (50A × 1.25 = 62.5A), which corresponds to a standard 63A circuit breaker.