650 Amp Wire Size at 150 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.53%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.14V (1.73%)
Voltage at Load End238.8 VLoss: 1.25 V (815.8 W)
Power & Breaker (125%)156.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 150 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A611.5 V (254.79%)0.0 V1008.7 V (420.29%)397478.2 WDrop/Amp High
12 AWG3.31 mm²20 A384.27 V (160.11%)0.0 V633.86 V (264.11%)249774.9 WDrop/Amp High
10 AWG5.26 mm²30 A241.81 V (100.75%)0.0 V398.88 V (166.2%)157177.7 WDrop/Amp High
8 AWG8.37 mm²50 A151.96 V (63.32%)88.0 V250.67 V (104.44%)98776.0 WDrop/Amp High
6 AWG13.3 mm²65 A95.63 V (39.85%)144.4 V157.75 V (65.73%)62162.0 WDrop/Amp High
4 AWG21.15 mm²85 A60.14 V (25.06%)179.9 V99.2 V (41.33%)39090.1 WDrop/Amp High
3 AWG26.67 mm²100 A47.69 V (19.87%)192.3 V78.67 V (32.78%)30999.4 WDrop/Amp High
2 AWG33.62 mm²115 A37.83 V (15.76%)202.2 V62.41 V (26.0%)24591.2 WDrop/Amp High
1 AWG42.41 mm²130 A29.99 V (12.5%)210.0 V49.47 V (20.61%)19494.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A23.78 V (9.91%)216.2 V39.22 V (16.34%)15456.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A18.86 V (7.86%)221.1 V31.12 V (12.96%)12260.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A14.96 V (6.23%)225.0 V24.68 V (10.28%)9725.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A11.87 V (4.94%)228.1 V19.57 V (8.15%)7712.3 WDrop/Amp High
250 kcmil126.7 mm²255 A10.04 V (4.18%)230.0 V16.56 V (6.9%)6525.3 WDrop/Amp High
300 kcmil152.0 mm²285 A8.37 V (3.49%)231.6 V13.8 V (5.75%)5439.2 WDrop/Amp High
350 kcmil177.3 mm²310 A7.17 V (2.99%)232.8 V11.83 V (4.93%)4663.0 WDrop/Amp High
400 kcmil202.7 mm²335 A6.27 V (2.61%)233.7 V10.35 V (4.31%)4078.7 WDrop/Amp High
500 kcmil253.4 mm²380 A5.02 V (2.09%)235.0 V8.28 V (3.45%)3262.6 WDrop/Amp High
600 kcmil304.0 mm²420 A4.18 V (1.74%)235.8 V6.9 V (2.88%)2719.6 WDrop/Amp High
750 kcmil380.0 mm²475 A3.35 V (1.39%)236.7 V5.52 V (2.3%)2175.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.51 V (1.05%)237.5 V4.14 V (1.73%)1631.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 150 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 150 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.25V (0.53%) and delivers 238.8V at the load.

What size aluminum wire is required for 650 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.14V (1.73%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.