🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 175 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.61%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.83V (2.01%)
Voltage at Load End238.5 VLoss: 1.47 V (951.8 W)
Power & Breaker (125%)156.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A713.42 V (297.26%)0.0 V1176.81 V (490.34%)463724.6 WDrop/Amp High
12 AWG3.31 mm²20 A448.31 V (186.8%)0.0 V739.51 V (308.13%)291404.0 WDrop/Amp High
10 AWG5.26 mm²30 A282.11 V (117.55%)0.0 V465.36 V (193.9%)183374.0 WDrop/Amp High
8 AWG8.37 mm²50 A177.29 V (73.87%)62.7 V292.45 V (121.85%)115238.6 WDrop/Amp High
6 AWG13.3 mm²65 A111.57 V (46.49%)128.4 V184.04 V (76.68%)72522.3 WDrop/Amp High
4 AWG21.15 mm²85 A70.16 V (29.23%)169.8 V115.73 V (48.22%)45605.1 WDrop/Amp High
3 AWG26.67 mm²100 A55.64 V (23.18%)184.4 V91.78 V (38.24%)36166.0 WDrop/Amp High
2 AWG33.62 mm²115 A44.14 V (18.39%)195.9 V72.81 V (30.34%)28689.7 WDrop/Amp High
1 AWG42.41 mm²130 A34.99 V (14.58%)205.0 V57.72 V (24.05%)22743.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A27.74 V (11.56%)212.3 V45.76 V (19.07%)18032.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A22.01 V (9.17%)218.0 V36.3 V (15.13%)14304.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A17.46 V (7.27%)222.5 V28.79 V (12.0%)11346.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A13.84 V (5.77%)226.2 V22.83 V (9.51%)8997.6 WDrop/Amp High
250 kcmil126.7 mm²255 A11.71 V (4.88%)228.3 V19.32 V (8.05%)7612.8 WDrop/Amp High
300 kcmil152.0 mm²285 A9.76 V (4.07%)230.2 V16.1 V (6.71%)6345.7 WDrop/Amp High
350 kcmil177.3 mm²310 A8.37 V (3.49%)231.6 V13.81 V (5.75%)5440.2 WDrop/Amp High
400 kcmil202.7 mm²335 A7.32 V (3.05%)232.7 V12.08 V (5.03%)4758.5 WDrop/Amp High
500 kcmil253.4 mm²380 A5.86 V (2.44%)234.1 V9.66 V (4.02%)3806.4 WDrop/Amp High
600 kcmil304.0 mm²420 A4.88 V (2.03%)235.1 V8.05 V (3.35%)3172.9 WDrop/Amp High
750 kcmil380.0 mm²475 A3.91 V (1.63%)236.1 V6.44 V (2.68%)2538.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.93 V (1.22%)237.1 V4.83 V (2.01%)1903.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 175 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.47V (0.61%) and delivers 238.5V at the load.

What size aluminum wire is required for 650 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.83V (2.01%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.