🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 120 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.42%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.31V (1.38%)
Voltage at Load End239.0 VLoss: 1.0 V (652.6 W)
Power & Breaker (125%)156.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 120 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A489.2 V (203.83%)0.0 V806.96 V (336.23%)317982.6 WDrop/Amp High
12 AWG3.31 mm²20 A307.42 V (128.09%)0.0 V507.09 V (211.29%)199819.9 WDrop/Amp High
10 AWG5.26 mm²30 A193.45 V (80.6%)46.6 V319.1 V (132.96%)125742.2 WDrop/Amp High
8 AWG8.37 mm²50 A121.57 V (50.65%)118.4 V200.53 V (83.56%)79020.8 WDrop/Amp High
6 AWG13.3 mm²65 A76.51 V (31.88%)163.5 V126.2 V (52.58%)49729.6 WDrop/Amp High
4 AWG21.15 mm²85 A48.11 V (20.05%)191.9 V79.36 V (33.07%)31272.0 WDrop/Amp High
3 AWG26.67 mm²100 A38.15 V (15.9%)201.8 V62.93 V (26.22%)24799.5 WDrop/Amp High
2 AWG33.62 mm²115 A30.27 V (12.61%)209.7 V49.92 V (20.8%)19672.9 WDrop/Amp High
1 AWG42.41 mm²130 A23.99 V (10.0%)216.0 V39.58 V (16.49%)15595.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A19.02 V (7.93%)221.0 V31.38 V (13.07%)12365.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A15.09 V (6.29%)224.9 V24.89 V (10.37%)9808.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A11.97 V (4.99%)228.0 V19.74 V (8.23%)7780.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A9.49 V (3.96%)230.5 V15.66 V (6.52%)6169.8 WDrop/Amp High
250 kcmil126.7 mm²255 A8.03 V (3.35%)232.0 V13.25 V (5.52%)5220.2 WDrop/Amp High
300 kcmil152.0 mm²285 A6.69 V (2.79%)233.3 V11.04 V (4.6%)4351.3 WDrop/Amp High
350 kcmil177.3 mm²310 A5.74 V (2.39%)234.3 V9.47 V (3.94%)3730.4 WDrop/Amp High
400 kcmil202.7 mm²335 A5.02 V (2.09%)235.0 V8.28 V (3.45%)3263.0 WDrop/Amp High
500 kcmil253.4 mm²380 A4.02 V (1.67%)236.0 V6.62 V (2.76%)2610.1 WDrop/Amp High
600 kcmil304.0 mm²420 A3.35 V (1.39%)236.7 V5.52 V (2.3%)2175.7 WDrop/Amp High
750 kcmil380.0 mm²475 A2.68 V (1.12%)237.3 V4.42 V (1.84%)1740.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.01 V (0.84%)238.0 V3.31 V (1.38%)1305.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 120 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 120 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.0V (0.42%) and delivers 239.0V at the load.

What size aluminum wire is required for 650 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.31V (1.38%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.