🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

70 Amp Wire Size at 175 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 70 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.73%
Aluminum Wire (≤3% Drop)2 AWGDrop: 6.79V (2.83%)
Voltage at Load End233.5 VLoss: 6.54 V (793.4 W)
Power & Breaker (125%)29.1 kW90A Breaker Recommended

All AWG & kcmil Wire Gauges for 70 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A66.54 V (27.72%)173.5 V109.75 V (45.73%)8067.2 WDrop/Amp High
12 AWG3.31 mm²20 A41.81 V (17.42%)198.2 V68.97 V (28.74%)5069.4 WDrop/Amp High
10 AWG5.26 mm²30 A26.31 V (10.96%)213.7 V43.4 V (18.08%)3190.1 WDrop/Amp High
8 AWG8.37 mm²50 A16.53 V (6.89%)223.5 V27.27 V (11.36%)2004.7 WDrop/Amp High
6 AWG13.3 mm²65 A10.41 V (4.34%)229.6 V17.16 V (7.15%)1261.6 WDrop/Amp High
4 AWG21.15 mm²85 A6.54 V (2.73%)233.5 V10.79 V (4.5%)793.4 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A5.19 V (2.16%)234.8 V8.56 V (3.57%)629.2 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A4.12 V (1.72%)235.9 V6.79 V (2.83%)499.1 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A3.26 V (1.36%)236.7 V5.38 V (2.24%)395.7 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.59 V (1.08%)237.4 V4.27 V (1.78%)313.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.05 V (0.86%)237.9 V3.39 V (1.41%)248.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.63 V (0.68%)238.4 V2.69 V (1.12%)197.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.29 V (0.54%)238.7 V2.13 V (0.89%)156.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.09 V (0.46%)238.9 V1.8 V (0.75%)132.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.91 V (0.38%)239.1 V1.5 V (0.63%)110.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.78 V (0.33%)239.2 V1.29 V (0.54%)94.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.68 V (0.28%)239.3 V1.13 V (0.47%)82.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.55 V (0.23%)239.5 V0.9 V (0.38%)66.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.46 V (0.19%)239.5 V0.75 V (0.31%)55.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.36 V (0.15%)239.6 V0.6 V (0.25%)44.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.27 V (0.11%)239.7 V0.45 V (0.19%)33.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 70 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 70A load over 175 feet one-way at 240V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 6.54V (2.73%) and delivers 233.5V at the load.

What size aluminum wire is required for 70 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 6.79V (2.83%).

What breaker size is needed for a 70A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (70A × 1.25 = 87.5A), which corresponds to a standard 90A circuit breaker.