⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

70 Amp Wire Size at 20 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 70 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 0.31%
Aluminum Wire (≤3% Drop)3 AWGDrop: 0.98V (0.41%)
Voltage at Load End239.3 VLoss: 0.75 V (90.7 W)
Power & Breaker (125%)29.1 kW90A Breaker Recommended

All AWG & kcmil Wire Gauges for 70 Amps at 20 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A7.6 V (3.17%)232.4 V12.54 V (5.23%)922.0 WDrop/Amp High
12 AWG3.31 mm²20 A4.78 V (1.99%)235.2 V7.88 V (3.28%)579.4 WDrop/Amp High
10 AWG5.26 mm²30 A3.01 V (1.25%)237.0 V4.96 V (2.07%)364.6 WDrop/Amp High
8 AWG8.37 mm²50 A1.89 V (0.79%)238.1 V3.12 V (1.3%)229.1 WDrop/Amp High
6 AWG13.3 mm²65 A1.19 V (0.5%)238.8 V1.96 V (0.82%)144.2 WDrop/Amp High
4 AWG21.15 mm²85 A0.75 V (0.31%)239.3 V1.23 V (0.51%)90.7 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.59 V (0.25%)239.4 V0.98 V (0.41%)71.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.47 V (0.2%)239.5 V0.78 V (0.32%)57.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.37 V (0.16%)239.6 V0.62 V (0.26%)45.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.3 V (0.12%)239.7 V0.49 V (0.2%)35.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.23 V (0.1%)239.8 V0.39 V (0.16%)28.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.19 V (0.08%)239.8 V0.31 V (0.13%)22.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.15 V (0.06%)239.9 V0.24 V (0.1%)17.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.12 V (0.05%)239.9 V0.21 V (0.09%)15.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.1 V (0.04%)239.9 V0.17 V (0.07%)12.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.09 V (0.04%)239.9 V0.15 V (0.06%)10.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.08 V (0.03%)239.9 V0.13 V (0.05%)9.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.06 V (0.03%)239.9 V0.1 V (0.04%)7.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.05 V (0.02%)239.9 V0.09 V (0.04%)6.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.04 V (0.02%)240.0 V0.07 V (0.03%)5.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.03 V (0.01%)240.0 V0.05 V (0.02%)3.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 70 amps at 20 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 70A load over 20 feet one-way at 240V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 0.75V (0.31%) and delivers 239.3V at the load.

What size aluminum wire is required for 70 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 3 AWG to maintain voltage drop at 0.98V (0.41%).

What breaker size is needed for a 70A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (70A × 1.25 = 87.5A), which corresponds to a standard 90A circuit breaker.