🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

70 Amp Wire Size at 50 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 70 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 0.9%
Aluminum Wire (≤3% Drop)3 AWGDrop: 2.45V (1.18%)
Voltage at Load End206.1 VLoss: 1.87 V (226.7 W)
Power & Breaker (125%)25.22 kW90A Breaker Recommended

All AWG & kcmil Wire Gauges for 70 Amps at 50 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A19.01 V (9.14%)189.0 V31.36 V (15.08%)2304.9 WDrop/Amp High
12 AWG3.31 mm²20 A11.95 V (5.74%)196.1 V19.71 V (9.47%)1448.4 WDrop/Amp High
10 AWG5.26 mm²30 A7.52 V (3.61%)200.5 V12.4 V (5.96%)911.4 WDrop/Amp High
8 AWG8.37 mm²50 A4.72 V (2.27%)203.3 V7.79 V (3.75%)572.8 WDrop/Amp High
6 AWG13.3 mm²65 A2.97 V (1.43%)205.0 V4.9 V (2.36%)360.5 WDrop/Amp High
4 AWG21.15 mm²85 A1.87 V (0.9%)206.1 V3.08 V (1.48%)226.7 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.48 V (0.71%)206.5 V2.45 V (1.18%)179.8 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.18 V (0.57%)206.8 V1.94 V (0.93%)142.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.93 V (0.45%)207.1 V1.54 V (0.74%)113.0 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.74 V (0.36%)207.3 V1.22 V (0.59%)89.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.59 V (0.28%)207.4 V0.97 V (0.47%)71.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.47 V (0.22%)207.5 V0.77 V (0.37%)56.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.37 V (0.18%)207.6 V0.61 V (0.29%)44.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.31 V (0.15%)207.7 V0.51 V (0.25%)37.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.26 V (0.13%)207.7 V0.43 V (0.21%)31.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.22 V (0.11%)207.8 V0.37 V (0.18%)27.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.2 V (0.09%)207.8 V0.32 V (0.15%)23.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.16 V (0.08%)207.8 V0.26 V (0.12%)18.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.13 V (0.06%)207.9 V0.21 V (0.1%)15.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.1 V (0.05%)207.9 V0.17 V (0.08%)12.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.08 V (0.04%)207.9 V0.13 V (0.06%)9.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 70 amps at 50 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 70A load over 50 feet one-way at 208V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 1.87V (0.9%) and delivers 206.1V at the load.

What size aluminum wire is required for 70 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 3 AWG to maintain voltage drop at 2.45V (1.18%).

What breaker size is needed for a 70A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (70A × 1.25 = 87.5A), which corresponds to a standard 90A circuit breaker.