70 Amp Wire Size at 600 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 70 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)250 kcmilDrop: 6.18V (2.97%)
Voltage at Load End202.4 VLoss: 5.58 V (676.7 W)
Power & Breaker (125%)25.22 kW90A Breaker Recommended

All AWG & kcmil Wire Gauges for 70 Amps at 600 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A228.13 V (109.68%)0.0 V376.3 V (180.91%)27658.8 WDrop/Amp High
12 AWG3.31 mm²20 A143.35 V (68.92%)64.6 V236.47 V (113.69%)17380.8 WDrop/Amp High
10 AWG5.26 mm²30 A90.21 V (43.37%)117.8 V148.8 V (71.54%)10937.3 WDrop/Amp High
8 AWG8.37 mm²50 A56.69 V (27.26%)151.3 V93.51 V (44.96%)6873.4 WDrop/Amp High
6 AWG13.3 mm²65 A35.68 V (17.15%)172.3 V58.85 V (28.29%)4325.6 WDrop/Amp High
4 AWG21.15 mm²85 A22.44 V (10.79%)185.6 V37.01 V (17.79%)2720.1 WDrop/Amp High
3 AWG26.67 mm²100 A17.79 V (8.55%)190.2 V29.35 V (14.11%)2157.1 WDrop/Amp High
2 AWG33.62 mm²115 A14.11 V (6.79%)193.9 V23.28 V (11.19%)1711.2 WDrop/Amp High
1 AWG42.41 mm²130 A11.19 V (5.38%)196.8 V18.46 V (8.87%)1356.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.87 V (4.26%)199.1 V14.63 V (7.03%)1075.5 W~ ≤5%
2/0 AWG67.43 mm²175 A7.04 V (3.38%)201.0 V11.61 V (5.58%)853.2 W~ ≤5%
3/0 AWG85.01 mm²200 A5.58 V (2.68%)202.4 V9.21 V (4.43%)676.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A4.43 V (2.13%)203.6 V7.3 V (3.51%)536.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.75 V (1.8%)204.3 V6.18 V (2.97%)454.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.12 V (1.5%)204.9 V5.15 V (2.48%)378.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.68 V (1.29%)205.3 V4.41 V (2.12%)324.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.34 V (1.13%)205.7 V3.86 V (1.86%)283.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.87 V (0.9%)206.1 V3.09 V (1.49%)227.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.56 V (0.75%)206.4 V2.57 V (1.24%)189.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.25 V (0.6%)206.8 V2.06 V (0.99%)151.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.94 V (0.45%)207.1 V1.54 V (0.74%)113.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 70 amps at 600 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 70A load over 600 feet one-way at 208V (3-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 5.58V (2.68%) and delivers 202.4V at the load.

What size aluminum wire is required for 70 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 250 kcmil to maintain voltage drop at 6.18V (2.97%).

What breaker size is needed for a 70A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (70A × 1.25 = 87.5A), which corresponds to a standard 90A circuit breaker.