⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 100 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.38%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.97V (1.24%)
Voltage at Load End239.1 VLoss: 0.9 V (630.8 W)
Power & Breaker (125%)168.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 100 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A439.03 V (182.93%)0.0 V724.19 V (301.75%)307320.5 WDrop/Amp High
12 AWG3.31 mm²20 A275.89 V (114.95%)0.0 V455.08 V (189.62%)193119.8 WDrop/Amp High
10 AWG5.26 mm²30 A173.61 V (72.34%)66.4 V286.37 V (119.32%)121526.0 WDrop/Amp High
8 AWG8.37 mm²50 A109.1 V (45.46%)130.9 V179.97 V (74.99%)76371.2 WDrop/Amp High
6 AWG13.3 mm²65 A68.66 V (28.61%)171.3 V113.26 V (47.19%)48062.1 WDrop/Amp High
4 AWG21.15 mm²85 A43.18 V (17.99%)196.8 V71.22 V (29.68%)30223.5 WDrop/Amp High
3 AWG26.67 mm²100 A34.24 V (14.27%)205.8 V56.48 V (23.53%)23968.0 WDrop/Amp High
2 AWG33.62 mm²115 A27.16 V (11.32%)212.8 V44.8 V (18.67%)19013.3 WDrop/Amp High
1 AWG42.41 mm²130 A21.53 V (8.97%)218.5 V35.52 V (14.8%)15072.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A17.07 V (7.11%)222.9 V28.16 V (11.73%)11950.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A13.54 V (5.64%)226.5 V22.34 V (9.31%)9479.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.74 V (4.48%)229.3 V17.72 V (7.38%)7519.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.52 V (3.55%)231.5 V14.05 V (5.85%)5962.9 WDrop/Amp High
250 kcmil126.7 mm²255 A7.21 V (3.0%)232.8 V11.89 V (4.95%)5045.2 WDrop/Amp High
300 kcmil152.0 mm²285 A6.01 V (2.5%)234.0 V9.91 V (4.13%)4205.4 WDrop/Amp High
350 kcmil177.3 mm²310 A5.15 V (2.15%)234.8 V8.5 V (3.54%)3605.3 WDrop/Amp High
400 kcmil202.7 mm²335 A4.51 V (1.88%)235.5 V7.43 V (3.1%)3153.6 WDrop/Amp High
500 kcmil253.4 mm²380 A3.6 V (1.5%)236.4 V5.94 V (2.48%)2522.6 WDrop/Amp High
600 kcmil304.0 mm²420 A3.0 V (1.25%)237.0 V4.96 V (2.06%)2102.7 WDrop/Amp High
750 kcmil380.0 mm²475 A2.4 V (1.0%)237.6 V3.96 V (1.65%)1682.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.8 V (0.75%)238.2 V2.97 V (1.24%)1261.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 100 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 100 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.9V (0.38%) and delivers 239.1V at the load.

What size aluminum wire is required for 700 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.97V (1.24%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.