🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 40 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.15%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.19V (0.5%)
Voltage at Load End239.6 VLoss: 0.36 V (252.3 W)
Power & Breaker (125%)168.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 40 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A175.61 V (73.17%)64.4 V289.68 V (120.7%)122928.2 WDrop/Amp High
12 AWG3.31 mm²20 A110.35 V (45.98%)129.6 V182.03 V (75.85%)77247.9 WDrop/Amp High
10 AWG5.26 mm²30 A69.44 V (28.93%)170.6 V114.55 V (47.73%)48610.4 WDrop/Amp High
8 AWG8.37 mm²50 A43.64 V (18.18%)196.4 V71.99 V (29.99%)30548.5 WDrop/Amp High
6 AWG13.3 mm²65 A27.46 V (11.44%)212.5 V45.3 V (18.88%)19224.9 WDrop/Amp High
4 AWG21.15 mm²85 A17.27 V (7.2%)222.7 V28.49 V (11.87%)12089.4 WDrop/Amp High
3 AWG26.67 mm²100 A13.7 V (5.71%)226.3 V22.59 V (9.41%)9587.2 WDrop/Amp High
2 AWG33.62 mm²115 A10.86 V (4.53%)229.1 V17.92 V (7.47%)7605.3 WDrop/Amp High
1 AWG42.41 mm²130 A8.61 V (3.59%)231.4 V14.21 V (5.92%)6029.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.83 V (2.85%)233.2 V11.26 V (4.69%)4780.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.42 V (2.26%)234.6 V8.94 V (3.72%)3791.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.3 V (1.79%)235.7 V7.09 V (2.95%)3007.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.41 V (1.42%)236.6 V5.62 V (2.34%)2385.2 WDrop/Amp High
250 kcmil126.7 mm²255 A2.88 V (1.2%)237.1 V4.76 V (1.98%)2018.1 WDrop/Amp High
300 kcmil152.0 mm²285 A2.4 V (1.0%)237.6 V3.96 V (1.65%)1682.2 WDrop/Amp High
350 kcmil177.3 mm²310 A2.06 V (0.86%)237.9 V3.4 V (1.42%)1442.1 WDrop/Amp High
400 kcmil202.7 mm²335 A1.8 V (0.75%)238.2 V2.97 V (1.24%)1261.4 WDrop/Amp High
500 kcmil253.4 mm²380 A1.44 V (0.6%)238.6 V2.38 V (0.99%)1009.0 WDrop/Amp High
600 kcmil304.0 mm²420 A1.2 V (0.5%)238.8 V1.98 V (0.83%)841.1 WDrop/Amp High
750 kcmil380.0 mm²475 A0.96 V (0.4%)239.0 V1.59 V (0.66%)672.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.72 V (0.3%)239.3 V1.19 V (0.5%)504.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 40 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 40 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.36V (0.15%) and delivers 239.6V at the load.

What size aluminum wire is required for 700 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.19V (0.5%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.