🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 30 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.12%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.89V (0.37%)
Voltage at Load End239.7 VLoss: 0.27 V (189.2 W)
Power & Breaker (125%)168.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 30 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A131.71 V (54.88%)108.3 V217.26 V (90.52%)92196.1 WDrop/Amp High
12 AWG3.31 mm²20 A82.77 V (34.49%)157.2 V136.52 V (56.89%)57935.9 WDrop/Amp High
10 AWG5.26 mm²30 A52.08 V (21.7%)187.9 V85.91 V (35.8%)36457.8 WDrop/Amp High
8 AWG8.37 mm²50 A32.73 V (13.64%)207.3 V53.99 V (22.5%)22911.3 WDrop/Amp High
6 AWG13.3 mm²65 A20.6 V (8.58%)219.4 V33.98 V (14.16%)14418.6 WDrop/Amp High
4 AWG21.15 mm²85 A12.95 V (5.4%)227.0 V21.37 V (8.9%)9067.0 WDrop/Amp High
3 AWG26.67 mm²100 A10.27 V (4.28%)229.7 V16.94 V (7.06%)7190.4 WDrop/Amp High
2 AWG33.62 mm²115 A8.15 V (3.4%)231.9 V13.44 V (5.6%)5704.0 WDrop/Amp High
1 AWG42.41 mm²130 A6.46 V (2.69%)233.5 V10.66 V (4.44%)4521.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.12 V (2.13%)234.9 V8.45 V (3.52%)3585.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.06 V (1.69%)235.9 V6.7 V (2.79%)2844.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.22 V (1.34%)236.8 V5.32 V (2.21%)2255.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.56 V (1.06%)237.4 V4.22 V (1.76%)1788.9 WDrop/Amp High
250 kcmil126.7 mm²255 A2.16 V (0.9%)237.8 V3.57 V (1.49%)1513.6 WDrop/Amp High
300 kcmil152.0 mm²285 A1.8 V (0.75%)238.2 V2.97 V (1.24%)1261.6 WDrop/Amp High
350 kcmil177.3 mm²310 A1.55 V (0.64%)238.5 V2.55 V (1.06%)1081.6 WDrop/Amp High
400 kcmil202.7 mm²335 A1.35 V (0.56%)238.6 V2.23 V (0.93%)946.1 WDrop/Amp High
500 kcmil253.4 mm²380 A1.08 V (0.45%)238.9 V1.78 V (0.74%)756.8 WDrop/Amp High
600 kcmil304.0 mm²420 A0.9 V (0.38%)239.1 V1.49 V (0.62%)630.8 WDrop/Amp High
750 kcmil380.0 mm²475 A0.72 V (0.3%)239.3 V1.19 V (0.5%)504.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.54 V (0.23%)239.5 V0.89 V (0.37%)378.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 30 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 30 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.27V (0.12%) and delivers 239.7V at the load.

What size aluminum wire is required for 700 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.89V (0.37%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.