750 Amp Wire Size at 175 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 750 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)10× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.82%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.57V (46.45%)
Voltage at Load End11.7 VLoss: 0.34 V (253.4 W)
Power & Breaker (125%)9.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 750 Amps at 175 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A823.18 V (6859.83%)0.0 V1357.86 V (11315.52%)617384.9 WDrop/Amp High
12 AWG3.31 mm²20 A517.29 V (4310.71%)0.0 V853.28 V (7110.66%)387963.9 WDrop/Amp High
10 AWG5.26 mm²30 A325.52 V (2712.63%)0.0 V536.95 V (4474.58%)244137.0 WDrop/Amp High
8 AWG8.37 mm²50 A204.57 V (1704.71%)0.0 V337.44 V (2811.98%)153424.2 WDrop/Amp High
6 AWG13.3 mm²65 A128.74 V (1072.82%)0.0 V212.36 V (1769.64%)96553.4 WDrop/Amp High
4 AWG21.15 mm²85 A80.96 V (674.63%)0.0 V133.54 V (1112.83%)60716.8 WDrop/Amp High
3 AWG26.67 mm²100 A64.2 V (535.0%)0.0 V105.9 V (882.5%)48150.0 WDrop/Amp High
2 AWG33.62 mm²115 A50.93 V (424.4%)0.0 V84.01 V (700.07%)38196.3 WDrop/Amp High
1 AWG42.41 mm²130 A40.37 V (336.44%)0.0 V66.6 V (554.97%)30279.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A32.01 V (266.75%)0.0 V52.8 V (440.01%)24007.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A25.39 V (211.6%)0.0 V41.89 V (349.05%)19044.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A20.14 V (167.84%)0.0 V33.22 V (276.86%)15106.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A15.97 V (133.1%)0.0 V26.35 V (219.55%)11979.1 WDrop/Amp High
250 kcmil126.7 mm²255 A13.51 V (112.62%)0.0 V22.29 V (185.76%)10135.4 WDrop/Amp High
300 kcmil152.0 mm²285 A11.26 V (93.87%)0.7 V18.58 V (154.84%)8448.4 WDrop/Amp High
350 kcmil177.3 mm²310 A9.66 V (80.48%)2.3 V15.93 V (132.75%)7242.9 WDrop/Amp High
400 kcmil202.7 mm²335 A8.45 V (70.39%)3.6 V13.93 V (116.11%)6335.3 WDrop/Amp High
500 kcmil253.4 mm²380 A6.76 V (56.31%)5.2 V11.15 V (92.88%)5067.7 WDrop/Amp High
600 kcmil304.0 mm²420 A5.63 V (46.94%)6.4 V9.29 V (77.42%)4224.2 WDrop/Amp High
750 kcmil380.0 mm²475 A4.51 V (37.55%)7.5 V7.43 V (61.94%)3379.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.38 V (28.16%)8.6 V5.57 V (46.45%)2534.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 750 amps at 175 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 750A load over 175 feet one-way at 12V (DC), you need 10× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.34V (2.82%) and delivers 11.7V at the load.

What size aluminum wire is required for 750 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.57V (46.45%).

What breaker size is needed for a 750A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (750A × 1.25 = 937.5A), which corresponds to a standard 1000A circuit breaker.