🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

150 Amp Wire Size at 175 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 150 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.81%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.11V (9.29%)
Voltage at Load End11.7 VLoss: 0.34 V (50.7 W)
Power & Breaker (125%)1.8 kW200A Breaker Recommended

All AWG & kcmil Wire Gauges for 150 Amps at 175 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A164.64 V (1371.97%)0.0 V271.57 V (2263.1%)24695.4 WDrop/Amp High
12 AWG3.31 mm²20 A103.46 V (862.14%)0.0 V170.66 V (1422.13%)15518.6 WDrop/Amp High
10 AWG5.26 mm²30 A65.1 V (542.53%)0.0 V107.39 V (894.92%)9765.5 WDrop/Amp High
8 AWG8.37 mm²50 A40.91 V (340.94%)0.0 V67.49 V (562.4%)6137.0 WDrop/Amp High
6 AWG13.3 mm²65 A25.75 V (214.56%)0.0 V42.47 V (353.93%)3862.1 WDrop/Amp High
4 AWG21.15 mm²85 A16.19 V (134.93%)0.0 V26.71 V (222.57%)2428.7 WDrop/Amp High
3 AWG26.67 mm²100 A12.84 V (107.0%)0.0 V21.18 V (176.5%)1926.0 WDrop/Amp High
2 AWG33.62 mm²115 A10.19 V (84.88%)1.8 V16.8 V (140.01%)1527.9 WDrop/Amp High
1 AWG42.41 mm²130 A8.07 V (67.29%)3.9 V13.32 V (110.99%)1211.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.4 V (53.35%)5.6 V10.56 V (88.0%)960.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.08 V (42.32%)6.9 V8.38 V (69.81%)761.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.03 V (33.57%)8.0 V6.64 V (55.37%)604.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.19 V (26.62%)8.8 V5.27 V (43.91%)479.2 WDrop/Amp High
250 kcmil126.7 mm²255 A2.7 V (22.52%)9.3 V4.46 V (37.15%)405.4 WDrop/Amp High
300 kcmil152.0 mm²285 A2.25 V (18.77%)9.7 V3.72 V (30.97%)337.9 WDrop/Amp High
350 kcmil177.3 mm²310 A1.93 V (16.1%)10.1 V3.19 V (26.55%)289.7 WDrop/Amp High
400 kcmil202.7 mm²335 A1.69 V (14.08%)10.3 V2.79 V (23.22%)253.4 WDrop/Amp High
500 kcmil253.4 mm²380 A1.35 V (11.26%)10.6 V2.23 V (18.58%)202.7 WDrop/Amp High
600 kcmil304.0 mm²420 A1.13 V (9.39%)10.9 V1.86 V (15.48%)169.0 WDrop/Amp High
750 kcmil380.0 mm²475 A0.9 V (7.51%)11.1 V1.49 V (12.39%)135.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.68 V (5.63%)11.3 V1.11 V (9.29%)101.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 150 amps at 175 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 150A load over 175 feet one-way at 12V (DC), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.34V (2.81%) and delivers 11.7V at the load.

What size aluminum wire is required for 150 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.11V (9.29%).

What breaker size is needed for a 150A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (150A × 1.25 = 187.5A), which corresponds to a standard 200A circuit breaker.