🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 175 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.35%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.93V (7.74%)
Voltage at Load End11.7 VLoss: 0.28 V (35.2 W)
Power & Breaker (125%)1.5 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 175 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A137.2 V (1143.31%)0.0 V226.31 V (1885.92%)17149.6 WDrop/Amp High
12 AWG3.31 mm²20 A86.21 V (718.45%)0.0 V142.21 V (1185.11%)10776.8 WDrop/Amp High
10 AWG5.26 mm²30 A54.25 V (452.11%)0.0 V89.49 V (745.76%)6781.6 WDrop/Amp High
8 AWG8.37 mm²50 A34.09 V (284.12%)0.0 V56.24 V (468.66%)4261.8 WDrop/Amp High
6 AWG13.3 mm²65 A21.46 V (178.8%)0.0 V35.39 V (294.94%)2682.0 WDrop/Amp High
4 AWG21.15 mm²85 A13.49 V (112.44%)0.0 V22.26 V (185.47%)1686.6 WDrop/Amp High
3 AWG26.67 mm²100 A10.7 V (89.17%)1.3 V17.65 V (147.08%)1337.5 WDrop/Amp High
2 AWG33.62 mm²115 A8.49 V (70.73%)3.5 V14.0 V (116.68%)1061.0 WDrop/Amp High
1 AWG42.41 mm²130 A6.73 V (56.07%)5.3 V11.1 V (92.49%)841.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.33 V (44.46%)6.7 V8.8 V (73.34%)666.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.23 V (35.27%)7.8 V6.98 V (58.17%)529.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.36 V (27.97%)8.6 V5.54 V (46.14%)419.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.66 V (22.18%)9.3 V4.39 V (36.59%)332.8 WDrop/Amp High
250 kcmil126.7 mm²255 A2.25 V (18.77%)9.7 V3.72 V (30.96%)281.5 WDrop/Amp High
300 kcmil152.0 mm²285 A1.88 V (15.65%)10.1 V3.1 V (25.81%)234.7 WDrop/Amp High
350 kcmil177.3 mm²310 A1.61 V (13.41%)10.4 V2.65 V (22.12%)201.2 WDrop/Amp High
400 kcmil202.7 mm²335 A1.41 V (11.73%)10.6 V2.32 V (19.35%)176.0 WDrop/Amp High
500 kcmil253.4 mm²380 A1.13 V (9.38%)10.9 V1.86 V (15.48%)140.8 WDrop/Amp High
600 kcmil304.0 mm²420 A0.94 V (7.82%)11.1 V1.55 V (12.9%)117.3 WDrop/Amp High
750 kcmil380.0 mm²475 A0.75 V (6.26%)11.2 V1.24 V (10.32%)93.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.56 V (4.69%)11.4 V0.93 V (7.74%)70.4 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 175 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 175 feet one-way at 12V (DC), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.28V (2.35%) and delivers 11.7V at the load.

What size aluminum wire is required for 125 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.93V (7.74%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.