⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

750 Amp Wire Size at 350 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 750 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.41%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.65V (4.64%)
Voltage at Load End205.1 VLoss: 2.92 V (3801.6 W)
Power & Breaker (125%)270.2 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 750 Amps at 350 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1425.79 V (685.48%)0.0 V2351.89 V (1130.71%)1852154.6 WDrop/Amp High
12 AWG3.31 mm²20 A895.96 V (430.75%)0.0 V1477.92 V (710.54%)1163891.7 WDrop/Amp High
10 AWG5.26 mm²30 A563.81 V (271.06%)0.0 V930.02 V (447.13%)732410.9 WDrop/Amp High
8 AWG8.37 mm²50 A354.32 V (170.35%)0.0 V584.46 V (280.99%)460272.6 WDrop/Amp High
6 AWG13.3 mm²65 A222.98 V (107.2%)0.0 V367.81 V (176.83%)289660.3 WDrop/Amp High
4 AWG21.15 mm²85 A140.22 V (67.41%)67.8 V231.3 V (111.2%)182150.4 WDrop/Amp High
3 AWG26.67 mm²100 A111.2 V (53.46%)96.8 V183.42 V (88.18%)144450.0 WDrop/Amp High
2 AWG33.62 mm²115 A88.21 V (42.41%)119.8 V145.51 V (69.95%)114589.0 WDrop/Amp High
1 AWG42.41 mm²130 A69.93 V (33.62%)138.1 V115.35 V (55.46%)90839.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A55.44 V (26.66%)152.6 V91.45 V (43.97%)72022.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A43.98 V (21.14%)164.0 V72.55 V (34.88%)57133.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A34.89 V (16.77%)173.1 V57.55 V (27.67%)45318.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A27.66 V (13.3%)180.3 V45.63 V (21.94%)35937.3 WDrop/Amp High
250 kcmil126.7 mm²255 A23.41 V (11.25%)184.6 V38.61 V (18.56%)30406.3 WDrop/Amp High
300 kcmil152.0 mm²285 A19.51 V (9.38%)188.5 V32.18 V (15.47%)25345.3 WDrop/Amp High
350 kcmil177.3 mm²310 A16.73 V (8.04%)191.3 V27.59 V (13.27%)21728.6 WDrop/Amp High
400 kcmil202.7 mm²335 A14.63 V (7.03%)193.4 V24.13 V (11.6%)19005.8 WDrop/Amp High
500 kcmil253.4 mm²380 A11.7 V (5.63%)196.3 V19.31 V (9.28%)15203.2 WDrop/Amp High
600 kcmil304.0 mm²420 A9.76 V (4.69%)198.2 V16.09 V (7.74%)12672.6 WDrop/Amp High
750 kcmil380.0 mm²475 A7.8 V (3.75%)200.2 V12.87 V (6.19%)10138.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.85 V (2.81%)202.1 V9.65 V (4.64%)7603.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 750 amps at 350 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 750A load over 350 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.92V (1.41%) and delivers 205.1V at the load.

What size aluminum wire is required for 750 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.65V (4.64%).

What breaker size is needed for a 750A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (750A × 1.25 = 937.5A), which corresponds to a standard 1000A circuit breaker.