🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 350 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.8%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 5.36V (2.58%)
Voltage at Load End202.2 VLoss: 5.81 V (1258.8 W)
Power & Breaker (125%)45.03 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 350 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A237.63 V (114.25%)0.0 V391.98 V (188.45%)51448.7 WDrop/Amp High
12 AWG3.31 mm²20 A149.33 V (71.79%)58.7 V246.32 V (118.42%)32330.3 WDrop/Amp High
10 AWG5.26 mm²30 A93.97 V (45.18%)114.0 V155.0 V (74.52%)20344.7 WDrop/Amp High
8 AWG8.37 mm²50 A59.05 V (28.39%)148.9 V97.41 V (46.83%)12785.3 WDrop/Amp High
6 AWG13.3 mm²65 A37.16 V (17.87%)170.8 V61.3 V (29.47%)8046.1 WDrop/Amp High
4 AWG21.15 mm²85 A23.37 V (11.24%)184.6 V38.55 V (18.53%)5059.7 WDrop/Amp High
3 AWG26.67 mm²100 A18.53 V (8.91%)189.5 V30.57 V (14.7%)4012.5 WDrop/Amp High
2 AWG33.62 mm²115 A14.7 V (7.07%)193.3 V24.25 V (11.66%)3183.0 WDrop/Amp High
1 AWG42.41 mm²130 A11.65 V (5.6%)196.3 V19.22 V (9.24%)2523.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A9.24 V (4.44%)198.8 V15.24 V (7.33%)2000.6 W~ ≤5%
2/0 AWG67.43 mm²175 A7.33 V (3.52%)200.7 V12.09 V (5.81%)1587.0 W~ ≤5%
3/0 AWG85.01 mm²200 A5.81 V (2.8%)202.2 V9.59 V (4.61%)1258.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A4.61 V (2.22%)203.4 V7.61 V (3.66%)998.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.9 V (1.88%)204.1 V6.44 V (3.09%)844.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.25 V (1.56%)204.7 V5.36 V (2.58%)704.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.79 V (1.34%)205.2 V4.6 V (2.21%)603.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.44 V (1.17%)205.6 V4.02 V (1.93%)527.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.95 V (0.94%)206.0 V3.22 V (1.55%)422.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.63 V (0.78%)206.4 V2.68 V (1.29%)352.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.3 V (0.63%)206.7 V2.15 V (1.03%)281.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.98 V (0.47%)207.0 V1.61 V (0.77%)211.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 350 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 350 feet one-way at 208V (3-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 5.81V (2.8%) and delivers 202.2V at the load.

What size aluminum wire is required for 125 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 5.36V (2.58%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.