⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 350 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 2.85%
Aluminum Wire (≤3% Drop)1 AWGDrop: 6.15V (2.96%)
Voltage at Load End202.1 VLoss: 5.93 V (410.9 W)
Power & Breaker (125%)14.41 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 350 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A76.04 V (36.56%)132.0 V125.43 V (60.3%)5268.4 WDrop/Amp High
12 AWG3.31 mm²20 A47.78 V (22.97%)160.2 V78.82 V (37.9%)3310.6 WDrop/Amp High
10 AWG5.26 mm²30 A30.07 V (14.46%)177.9 V49.6 V (23.85%)2083.3 WDrop/Amp High
8 AWG8.37 mm²50 A18.9 V (9.09%)189.1 V31.17 V (14.99%)1309.2 WDrop/Amp High
6 AWG13.3 mm²65 A11.89 V (5.72%)196.1 V19.62 V (9.43%)823.9 WDrop/Amp High
4 AWG21.15 mm²85 A7.48 V (3.6%)200.5 V12.34 V (5.93%)518.1 W~ ≤5%
3 AWG26.67 mm²100 A5.93 V (2.85%)202.1 V9.78 V (4.7%)410.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A4.7 V (2.26%)203.3 V7.76 V (3.73%)325.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A3.73 V (1.79%)204.3 V6.15 V (2.96%)258.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.96 V (1.42%)205.0 V4.88 V (2.34%)204.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.35 V (1.13%)205.7 V3.87 V (1.86%)162.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.86 V (0.89%)206.1 V3.07 V (1.48%)128.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.48 V (0.71%)206.5 V2.43 V (1.17%)102.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.25 V (0.6%)206.8 V2.06 V (0.99%)86.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.04 V (0.5%)207.0 V1.72 V (0.83%)72.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.89 V (0.43%)207.1 V1.47 V (0.71%)61.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.78 V (0.38%)207.2 V1.29 V (0.62%)54.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.62 V (0.3%)207.4 V1.03 V (0.5%)43.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.52 V (0.25%)207.5 V0.86 V (0.41%)36.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.42 V (0.2%)207.6 V0.69 V (0.33%)28.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.31 V (0.15%)207.7 V0.51 V (0.25%)21.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 350 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 350 feet one-way at 208V (3-Phase), you need 3 AWG copper wire. This produces a voltage drop of 5.93V (2.85%) and delivers 202.1V at the load.

What size aluminum wire is required for 40 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1 AWG to maintain voltage drop at 6.15V (2.96%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.