⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

750 Amp Wire Size at 400 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 750 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.69%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 11.03V (2.3%)
Voltage at Load End476.6 VLoss: 3.35 V (4344.6 W)
Power & Breaker (125%)623.54 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 750 Amps at 400 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1629.47 V (339.47%)0.0 V2687.87 V (559.97%)2116748.1 WDrop/Amp High
12 AWG3.31 mm²20 A1023.96 V (213.32%)0.0 V1689.05 V (351.89%)1330161.9 WDrop/Amp High
10 AWG5.26 mm²30 A644.35 V (134.24%)0.0 V1062.88 V (221.43%)837041.1 WDrop/Amp High
8 AWG8.37 mm²50 A404.93 V (84.36%)75.1 V667.95 V (139.16%)526025.8 WDrop/Amp High
6 AWG13.3 mm²65 A254.83 V (53.09%)225.2 V420.36 V (87.57%)331040.3 WDrop/Amp High
4 AWG21.15 mm²85 A160.25 V (33.39%)319.7 V264.34 V (55.07%)208171.9 WDrop/Amp High
3 AWG26.67 mm²100 A127.08 V (26.48%)352.9 V209.63 V (43.67%)165085.7 WDrop/Amp High
2 AWG33.62 mm²115 A100.81 V (21.0%)379.2 V166.29 V (34.64%)130958.8 WDrop/Amp High
1 AWG42.41 mm²130 A79.92 V (16.65%)400.1 V131.83 V (27.46%)103816.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A63.36 V (13.2%)416.6 V104.52 V (21.77%)82311.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A50.26 V (10.47%)429.7 V82.91 V (17.27%)65294.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A39.87 V (8.31%)440.1 V65.77 V (13.7%)51792.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A31.62 V (6.59%)448.4 V52.15 V (10.87%)41071.2 WDrop/Amp High
250 kcmil126.7 mm²255 A26.75 V (5.57%)453.2 V44.13 V (9.19%)34750.1 WDrop/Amp High
300 kcmil152.0 mm²285 A22.3 V (4.65%)457.7 V36.78 V (7.66%)28966.0 WDrop/Amp High
350 kcmil177.3 mm²310 A19.12 V (3.98%)460.9 V31.53 V (6.57%)24832.7 WDrop/Amp High
400 kcmil202.7 mm²335 A16.72 V (3.48%)463.3 V27.58 V (5.75%)21720.9 WDrop/Amp High
500 kcmil253.4 mm²380 A13.38 V (2.79%)466.6 V22.06 V (4.6%)17375.0 WDrop/Amp High
600 kcmil304.0 mm²420 A11.15 V (2.32%)468.9 V18.39 V (3.83%)14483.0 WDrop/Amp High
750 kcmil380.0 mm²475 A8.92 V (1.86%)471.1 V14.71 V (3.07%)11586.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A6.69 V (1.39%)473.3 V11.03 V (2.3%)8689.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 750 amps at 400 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 750A load over 400 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.35V (0.69%) and delivers 476.6V at the load.

What size aluminum wire is required for 750 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 11.03V (2.3%).

What breaker size is needed for a 750A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (750A × 1.25 = 937.5A), which corresponds to a standard 1000A circuit breaker.