🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

750 Amp Wire Size at 450 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 750 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 12.41V (2.59%)
Voltage at Load End476.2 VLoss: 3.77 V (4887.7 W)
Power & Breaker (125%)623.54 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 750 Amps at 450 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1833.16 V (381.91%)0.0 V3023.85 V (629.97%)2381341.6 WDrop/Amp High
12 AWG3.31 mm²20 A1151.95 V (239.99%)0.0 V1900.19 V (395.87%)1496432.2 WDrop/Amp High
10 AWG5.26 mm²30 A724.9 V (151.02%)0.0 V1195.74 V (249.11%)941671.2 WDrop/Amp High
8 AWG8.37 mm²50 A455.55 V (94.91%)24.4 V751.45 V (156.55%)591779.0 WDrop/Amp High
6 AWG13.3 mm²65 A286.69 V (59.73%)193.3 V472.9 V (98.52%)372420.3 WDrop/Amp High
4 AWG21.15 mm²85 A180.28 V (37.56%)299.7 V297.38 V (61.95%)234193.4 WDrop/Amp High
3 AWG26.67 mm²100 A142.97 V (29.79%)337.0 V235.83 V (49.13%)185721.4 WDrop/Amp High
2 AWG33.62 mm²115 A113.41 V (23.63%)366.6 V187.08 V (38.97%)147328.7 WDrop/Amp High
1 AWG42.41 mm²130 A89.91 V (18.73%)390.1 V148.31 V (30.9%)116793.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A71.28 V (14.85%)408.7 V117.58 V (24.5%)92600.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A56.55 V (11.78%)423.5 V93.28 V (19.43%)73456.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A44.85 V (9.34%)435.1 V73.99 V (15.41%)58266.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A35.57 V (7.41%)444.4 V58.67 V (12.22%)46205.1 WDrop/Amp High
250 kcmil126.7 mm²255 A30.09 V (6.27%)449.9 V49.64 V (10.34%)39093.8 WDrop/Amp High
300 kcmil152.0 mm²285 A25.09 V (5.23%)454.9 V41.38 V (8.62%)32586.8 WDrop/Amp High
350 kcmil177.3 mm²310 A21.51 V (4.48%)458.5 V35.47 V (7.39%)27936.8 WDrop/Amp High
400 kcmil202.7 mm²335 A18.81 V (3.92%)461.2 V31.03 V (6.46%)24436.1 WDrop/Amp High
500 kcmil253.4 mm²380 A15.05 V (3.13%)465.0 V24.82 V (5.17%)19546.9 WDrop/Amp High
600 kcmil304.0 mm²420 A12.54 V (2.61%)467.5 V20.69 V (4.31%)16293.4 WDrop/Amp High
750 kcmil380.0 mm²475 A10.03 V (2.09%)470.0 V16.55 V (3.45%)13034.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A7.53 V (1.57%)472.5 V12.41 V (2.59%)9775.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 750 amps at 450 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 750A load over 450 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.77V (0.79%) and delivers 476.2V at the load.

What size aluminum wire is required for 750 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 12.41V (2.59%).

What breaker size is needed for a 750A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (750A × 1.25 = 937.5A), which corresponds to a standard 1000A circuit breaker.