🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

750 Amp Wire Size at 750 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 750 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.01%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 23.89V (9.95%)
Voltage at Load End235.2 VLoss: 4.83 V (3620.5 W)
Power & Breaker (125%)180.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 750 Amps at 750 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3527.91 V (1469.96%)0.0 V5819.41 V (2424.75%)2645935.1 WDrop/Amp High
12 AWG3.31 mm²20 A2216.94 V (923.72%)0.0 V3656.91 V (1523.71%)1662702.4 WDrop/Amp High
10 AWG5.26 mm²30 A1395.07 V (581.28%)0.0 V2301.21 V (958.84%)1046301.3 WDrop/Amp High
8 AWG8.37 mm²50 A876.71 V (365.3%)0.0 V1446.16 V (602.57%)657532.3 WDrop/Amp High
6 AWG13.3 mm²65 A551.73 V (229.89%)0.0 V910.1 V (379.21%)413800.4 WDrop/Amp High
4 AWG21.15 mm²85 A346.95 V (144.56%)0.0 V572.31 V (238.46%)260214.9 WDrop/Amp High
3 AWG26.67 mm²100 A275.14 V (114.64%)0.0 V453.86 V (189.11%)206357.1 WDrop/Amp High
2 AWG33.62 mm²115 A218.26 V (90.94%)21.7 V360.03 V (150.01%)163698.5 WDrop/Amp High
1 AWG42.41 mm²130 A173.03 V (72.09%)67.0 V285.41 V (118.92%)129770.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A137.19 V (57.16%)102.8 V226.29 V (94.29%)102889.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A108.82 V (45.34%)131.2 V179.51 V (74.8%)81618.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A86.32 V (35.97%)153.7 V142.39 V (59.33%)64740.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A68.45 V (28.52%)171.5 V112.91 V (47.05%)51339.0 WDrop/Amp High
250 kcmil126.7 mm²255 A57.92 V (24.13%)182.1 V95.54 V (39.81%)43437.6 WDrop/Amp High
300 kcmil152.0 mm²285 A48.28 V (20.12%)191.7 V79.63 V (33.18%)36207.5 WDrop/Amp High
350 kcmil177.3 mm²310 A41.39 V (17.24%)198.6 V68.27 V (28.45%)31040.9 WDrop/Amp High
400 kcmil202.7 mm²335 A36.2 V (15.08%)203.8 V59.72 V (24.88%)27151.2 WDrop/Amp High
500 kcmil253.4 mm²380 A28.96 V (12.07%)211.0 V47.77 V (19.9%)21718.8 WDrop/Amp High
600 kcmil304.0 mm²420 A24.14 V (10.06%)215.9 V39.82 V (16.59%)18103.8 WDrop/Amp High
750 kcmil380.0 mm²475 A19.31 V (8.05%)220.7 V31.85 V (13.27%)14483.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A14.48 V (6.03%)225.5 V23.89 V (9.95%)10861.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 750 amps at 750 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 750A load over 750 feet one-way at 240V (1-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.83V (2.01%) and delivers 235.2V at the load.

What size aluminum wire is required for 750 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 23.89V (9.95%).

What breaker size is needed for a 750A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (750A × 1.25 = 937.5A), which corresponds to a standard 1000A circuit breaker.