⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 150 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.65%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.1V (2.12%)
Voltage at Load End238.5 VLoss: 1.54 V (1235.8 W)
Power & Breaker (125%)192.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 150 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A752.62 V (313.59%)0.0 V1241.47 V (517.28%)602097.2 WDrop/Amp High
12 AWG3.31 mm²20 A472.95 V (197.06%)0.0 V780.14 V (325.06%)378357.2 WDrop/Amp High
10 AWG5.26 mm²30 A297.61 V (124.01%)0.0 V490.93 V (204.55%)238091.7 WDrop/Amp High
8 AWG8.37 mm²50 A187.03 V (77.93%)53.0 V308.51 V (128.55%)149625.1 WDrop/Amp High
6 AWG13.3 mm²65 A117.7 V (49.04%)122.3 V194.16 V (80.9%)94162.6 WDrop/Amp High
4 AWG21.15 mm²85 A74.02 V (30.84%)166.0 V122.09 V (50.87%)59213.3 WDrop/Amp High
3 AWG26.67 mm²100 A58.7 V (24.46%)181.3 V96.82 V (40.34%)46957.7 WDrop/Amp High
2 AWG33.62 mm²115 A46.56 V (19.4%)193.4 V76.81 V (32.0%)37250.5 WDrop/Amp High
1 AWG42.41 mm²130 A36.91 V (15.38%)203.1 V60.89 V (25.37%)29529.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A29.27 V (12.19%)210.7 V48.28 V (20.11%)23413.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A23.22 V (9.67%)216.8 V38.3 V (15.96%)18572.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A18.41 V (7.67%)221.6 V30.38 V (12.66%)14731.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A14.6 V (6.08%)225.4 V24.09 V (10.04%)11682.5 WDrop/Amp High
250 kcmil126.7 mm²255 A12.36 V (5.15%)227.6 V20.38 V (8.49%)9884.5 WDrop/Amp High
300 kcmil152.0 mm²285 A10.3 V (4.29%)229.7 V16.99 V (7.08%)8239.2 WDrop/Amp High
350 kcmil177.3 mm²310 A8.83 V (3.68%)231.2 V14.56 V (6.07%)7063.5 WDrop/Amp High
400 kcmil202.7 mm²335 A7.72 V (3.22%)232.3 V12.74 V (5.31%)6178.4 WDrop/Amp High
500 kcmil253.4 mm²380 A6.18 V (2.57%)233.8 V10.19 V (4.25%)4942.2 WDrop/Amp High
600 kcmil304.0 mm²420 A5.15 V (2.15%)234.9 V8.49 V (3.54%)4119.6 WDrop/Amp High
750 kcmil380.0 mm²475 A4.12 V (1.72%)235.9 V6.8 V (2.83%)3295.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.09 V (1.29%)236.9 V5.1 V (2.12%)2471.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 150 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 150 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.54V (0.65%) and delivers 238.5V at the load.

What size aluminum wire is required for 800 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.1V (2.12%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.