⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 175 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.75%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.95V (2.48%)
Voltage at Load End238.2 VLoss: 1.8 V (1441.8 W)
Power & Breaker (125%)192.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A878.06 V (365.86%)0.0 V1448.39 V (603.49%)702446.8 WDrop/Amp High
12 AWG3.31 mm²20 A551.77 V (229.9%)0.0 V910.16 V (379.24%)441416.7 WDrop/Amp High
10 AWG5.26 mm²30 A347.22 V (144.67%)0.0 V572.75 V (238.64%)277773.6 WDrop/Amp High
8 AWG8.37 mm²50 A218.2 V (90.92%)21.8 V359.93 V (149.97%)174562.6 WDrop/Amp High
6 AWG13.3 mm²65 A137.32 V (57.22%)102.7 V226.51 V (94.38%)109856.3 WDrop/Amp High
4 AWG21.15 mm²85 A86.35 V (35.98%)153.6 V142.44 V (59.35%)69082.2 WDrop/Amp High
3 AWG26.67 mm²100 A68.48 V (28.53%)171.5 V112.96 V (47.07%)54784.0 WDrop/Amp High
2 AWG33.62 mm²115 A54.32 V (22.63%)185.7 V89.61 V (37.34%)43458.9 WDrop/Amp High
1 AWG42.41 mm²130 A43.06 V (17.94%)196.9 V71.04 V (29.6%)34451.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A34.14 V (14.23%)205.9 V56.32 V (23.47%)27315.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A27.09 V (11.29%)212.9 V44.68 V (18.62%)21668.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A21.48 V (8.95%)218.5 V35.44 V (14.77%)17187.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A17.04 V (7.1%)223.0 V28.1 V (11.71%)13629.6 WDrop/Amp High
250 kcmil126.7 mm²255 A14.41 V (6.01%)225.6 V23.78 V (9.91%)11531.9 WDrop/Amp High
300 kcmil152.0 mm²285 A12.02 V (5.01%)228.0 V19.82 V (8.26%)9612.4 WDrop/Amp High
350 kcmil177.3 mm²310 A10.3 V (4.29%)229.7 V16.99 V (7.08%)8240.8 WDrop/Amp High
400 kcmil202.7 mm²335 A9.01 V (3.75%)231.0 V14.86 V (6.19%)7208.1 WDrop/Amp High
500 kcmil253.4 mm²380 A7.21 V (3.0%)232.8 V11.89 V (4.95%)5765.9 WDrop/Amp High
600 kcmil304.0 mm²420 A6.01 V (2.5%)234.0 V9.91 V (4.13%)4806.2 WDrop/Amp High
750 kcmil380.0 mm²475 A4.81 V (2.0%)235.2 V7.93 V (3.3%)3845.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.6 V (1.5%)236.4 V5.95 V (2.48%)2883.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 175 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.8V (0.75%) and delivers 238.2V at the load.

What size aluminum wire is required for 800 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.95V (2.48%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.