⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 40 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.17%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.36V (0.57%)
Voltage at Load End239.6 VLoss: 0.41 V (329.6 W)
Power & Breaker (125%)192.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 40 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A200.7 V (83.62%)39.3 V331.06 V (137.94%)160559.3 WDrop/Amp High
12 AWG3.31 mm²20 A126.12 V (52.55%)113.9 V208.04 V (86.68%)100895.2 WDrop/Amp High
10 AWG5.26 mm²30 A79.36 V (33.07%)160.6 V130.91 V (54.55%)63491.1 WDrop/Amp High
8 AWG8.37 mm²50 A49.88 V (20.78%)190.1 V82.27 V (34.28%)39900.0 WDrop/Amp High
6 AWG13.3 mm²65 A31.39 V (13.08%)208.6 V51.77 V (21.57%)25110.0 WDrop/Amp High
4 AWG21.15 mm²85 A19.74 V (8.22%)220.3 V32.56 V (13.57%)15790.2 WDrop/Amp High
3 AWG26.67 mm²100 A15.65 V (6.52%)224.3 V25.82 V (10.76%)12522.1 WDrop/Amp High
2 AWG33.62 mm²115 A12.42 V (5.17%)227.6 V20.48 V (8.53%)9933.5 WDrop/Amp High
1 AWG42.41 mm²130 A9.84 V (4.1%)230.2 V16.24 V (6.77%)7874.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.8 V (3.25%)232.2 V12.87 V (5.36%)6243.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.19 V (2.58%)233.8 V10.21 V (4.26%)4952.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.91 V (2.05%)235.1 V8.1 V (3.38%)3928.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.89 V (1.62%)236.1 V6.42 V (2.68%)3115.3 WDrop/Amp High
250 kcmil126.7 mm²255 A3.29 V (1.37%)236.7 V5.43 V (2.26%)2635.9 WDrop/Amp High
300 kcmil152.0 mm²285 A2.75 V (1.14%)237.3 V4.53 V (1.89%)2197.1 WDrop/Amp High
350 kcmil177.3 mm²310 A2.35 V (0.98%)237.6 V3.88 V (1.62%)1883.6 WDrop/Amp High
400 kcmil202.7 mm²335 A2.06 V (0.86%)237.9 V3.4 V (1.42%)1647.6 WDrop/Amp High
500 kcmil253.4 mm²380 A1.65 V (0.69%)238.4 V2.72 V (1.13%)1317.9 WDrop/Amp High
600 kcmil304.0 mm²420 A1.37 V (0.57%)238.6 V2.27 V (0.94%)1098.6 WDrop/Amp High
750 kcmil380.0 mm²475 A1.1 V (0.46%)238.9 V1.81 V (0.76%)878.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.82 V (0.34%)239.2 V1.36 V (0.57%)659.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 40 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 40 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.41V (0.17%) and delivers 239.6V at the load.

What size aluminum wire is required for 800 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.36V (0.57%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.